Maintenance and Repair
EN
10
Maintenance and Repair
EN
EN
EN
EN
EN
EN
EN
10.1 Maintenance
EN
• Consult the relevant national regulations to determine the type and extent of
EN
inspections.
EN
• Adapt inspection intervals to the operating conditions.
EN
During maintenance of the device, check at least:
EN
• if the conductors are clamped properly,
EN
• the compliance with the permissible temperatures (according to IEC/EN 60079),
EN
• whether the enclosure and seals are damaged,
• if the detachable connections, for example screws, are fitted tightly
EN
EN
10.2 Maintenance
EN
EN
EN
EN
EN
EN
EN
EN
12
SolConeX Plug, 16 A
Series 8570/12
Unauthorized work being performed on the device!
Risk of injuries and material damage!
• Work performed on the device must only be carried out by
appropriately authorized and trained personnel.
Danger due to live components!
Risk of severe injuries!
• All connections and wiring must be disconnected from the
power supply.
• Secure the connections against unauthorized switching.
Observe the relevant national regulations in the country of use.
• To avoid corrosion, the plug must be pulled regularly.
• If required, clean the plug pins.
• After 1000 mating cycles, it is recommended to clean and then lubricate
using the lubricating oil KLÜBERALFA KRA 3-730.
It is not allowed to use lubricating greases based on mineral oils!
WARNING
WARNING
227127 / 8570621300
2016-04-21·BA00·III·en·01