11 Appendix
Index
Parameter
60
HI_HI_ALM
49
HI_HI_LIM
48
HI_HI_PRI
51
HI_LIM
148
PID Function Block (PID controller)
Write access with
operating mode
(MODE_BLK)
ROUT - RCAS - CAS -
Alarm status display for the upper alarm limit value (HI_HI_LIM), including
AUTO -
details of the time of the alarm (date, time) and the value that triggered the
MAN - OOS
alarm.
2
In addition the active block alarm can be acknowledged in this parameter
group.
ROUT - RCAS - CAS -
Entry of the alarm limit value for the upper alarm (HI_HI_ALM). If the value PV
AUTO -
exceeds this limit value then the alarm status parameter HI_HI_ALM is
MAN - OOS
output.
User input:
Factory default:
2
If the setting for the end of the scale is changed in the parameter PV_SCALE
this value should be modified accordingly.
ROUT - RCAS - CAS -
Specifies the action taken when the upper alarm limit value (HI_HI_LIM) is
AUTO -
exceeded.
MAN - OOS
User input:
0
1
2
3-7
8-15
Factory default:
ROUT - RCAS - CAS -
Entry of the alarm limit value for the upper pre alarm (HI_ALM). If the value
AUTO -
PV exceeds this limit value then the alarm status parameter HI_ALM is
MAN - OOS
output.
User input:
Factory default:+ INF
2
If the setting for the end of the scale is changed in the parameter PV_SCALE
this value should be modified accordingly.
FOUNDATION Fieldbus temperature transmitter
Description
Note!
Range and unit of PV_SCALE
+ INF
Note!
=
The violation of the upper alarm limit is not evaluated.
=
No notification if the upper alarm limit value is infringed.
=
Reserved for block alarms.
=
The violation of the upper alarm limit is
output as a user notice with the appropriate priority
(3 = low priority, 7 = high priority).
=
The violation of the upper alarm limit is
output as a critical alarm with the appropriate priority
(8 = low priority, 15 = high priority).
0
Range and unit of PV_SCALE
Note!
Endress+Hauser