English
– Irradiation with HF Field,
single frequencies
IEC 60255-22-3, IEC 61000-4-3, Class III
amplitude-modulated
pulse-modulated
– Fast Transient Disturbance Variables/Burst
IEC 60255-22-4, IEC 61000-4-4,
Class IV
– High Energy Surge Voltages (SURGE)
IEC 61000-4-5, Installation Class 3
Power supply
Relay output (GOK)
Communication interfaces
– High Energy Surge Voltages (SURGE)
TBR14 (3), ETS 300046–3 Sect. 5.7.1
Communication interfaces
– Line Conducted HF, amplitude modulated
IEC 61000-4-6, Class III
– Power System Frequency Magnetic Field
IEC 61000-4-8, Class IV
IEC 60255-6
– Oscillatory Surge Withstand Capability
IEEE C37.90.1
– Fast Transient Surge Withstand Capability
IEEE C37.90.1
– Radiated Electromagnetic Interference
IEEE C37.90.2
– Damped Oscillations
IEC 60694, IEC 61000-4-12
66
All manuals and user guides at all-guides.com
10 V/m
80; 160; 450; 900 MHz; 80 % AM 1 kHz;
duty cycle > 10 s
900 MHz; 50 % PM,
repetition frequency 200 Hz
4 kV; 5/50 ns; 5 kHz; 100 kHz;
Burst length = 15 ms;
repetition rate 300 ms; both polarities;
R
i
Impuls: 1.2/50 µs
common mode: 2 kV; 12 Ω; 9 µF
diff. mode: 1 kV; 2 Ω; 18 µF
common mode: 2 kV; 42 Ω; 0.5 µF
common mode: 2 kV; 2 Ω; 18 µF
common mode: 2 kV; 15 Ω; 18 µF
10 V: 150 kHz to 80 MHz; 80 % AM; 1 kHz
30 A/m continuous; 300 A/m for 3 s; 50 Hz
0.5 mT; 50 Hz
2.5 kV (Peak Value); 1 MHz; τ = 15 ms;
400 surges per s; test duration 2 s;
R
i
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
repetition rate 300 ms; both polarities;
R
i
35 V/m; 80 MHz to 1000 MHz
2.5 kV (Peak Value), polarity alternating
100 kHz, 1 MHz, R
= 50 Ω; test duration 1 min
= 150 Ω
= 50 Ω; test duration 1 min
= 200 Ω
i
C53000-B1174-C173-5
7XV5461-0Bx00