7XV5461-0Bx00
Typical application area for the FO-Repeater is communication of the protection data
interface of 7SD52, 7SD610, 7SA52 and 7SA6 differential and distance protection devices.
Furthermore, serial data of the 7XV5 device series can be transferred over long distances.
The connection to the protection device is provided interference-proof by means of a fibre-
optic connection. The maximum optical transmission distance between the protection device
and FO-Repeater is specified to 1.5 km, when a 62.5/125 µm or 50/125 µm fibre-optic cable
is used.
The FO-Repeater supports easy commissioning of the entire communications path. The
loops for port 1/2 can be activated for commissioning so that the input signals are mirrored
on the respective port. The repeater has a relay contact to output a "device ready" signal
(DR) and has also a wide range power supply unit covering the entire normal DC and AC
auxiliary voltage range.
Note:
The operation with bidirectional FO-Repeaters offers the advantage that only
one fibre-optic cable is required for transmission in both directions. For this
purpose one device each is required with the order options - 0BL00 and
0BK00 (see ordering data). Devices with the same ordering numbers must
not be used in pairs.
DIGSI
DIGSI cable
7XV5100-4
RS232
Mini Star Coupler
7XV5450-0BA00
FOx
FOx
FOx
1)
SIPROTEC
SIEMENS
RUN
ERROR
L1 402,1A
Max450.1A
L2 402,1A
Max450.1A
L3 402,1A
Max450.1A
E
00.0A
Anr. L1
Anr. L2
Anr. L3
Anr. Erde
Automat
FO2
SIPROTEC
Repeater
7XV5461
LC connector
Long distance data transmission via multimode fibre up to 4/8 km
Long distance data transmission via singlemode fibre up to 24/60/100/170 km
Figure 3 Example: Protection data transmission and remote control of a device using an optical
wide area connection
C53000-B1174-C173-5
All manuals and user guides at all-guides.com
Station PC
Converter
7XV5101-0B
Modem
System modem
FO1
7XV58xx
FOx
1) Multimode fibre with ST plugs
on both sides (6XV8100)
1)
1)
SIPROTEC
SIEMENS
RUN
ERROR
L1 402,1A
Max450.1A
L2 402,1A
Max450.1A
L3 402,1A
Max450.1A
E
00.0A
1)
Anr. L1
Anr. L2
Anr. L3
Anr. Erde
Automat
FO1
SIPROTEC
FO1 = Protection data transfer
FO3
FO2 = Central / Remote control with DIGSI 4
Long-distance data transmission via monomode fibre up to 25 / 60 / 100 km
Private or public
telecommunication
Office PC
networks
Modem
Office modem
7XV58xx
1)
SIPROTEC
SIEMENS
RUN
ERROR
L1 402,1A
Max450.1A
L2 402,1A
Max450.1A
L3 402,1A
Max450.1A
E
00.0A
1)
Anr. L1
Anr. L2
Anr. L3
Anr. Erde
Automat
FO1
SIPROTEC
Repeater
7XV5461
FO3
English
DIGSI
Further devices
1)
or converters
FOx
FOx
FOx
FOx
Mini Star Coupler
SIEMENS
7XV5450-0BA00
L1 402,1A
L2 402,1A
L3 402,1A
E
FO1
RS232
Anr. L1
Anr. L2
Anr. L3
Anr. Erde
Automat
1)
FO2
SIPROTEC
LC connector
SIPROTEC
RUN
ERROR
Max450.1A
Max450.1A
Max450.1A
00.0A
45