9. Fault finding chart

Fault
Cause
The pump does not
The wires are not con-
react to the input
nected correctly to the
signal MIN, MAX or
terminal block.
10 V.
The plug connection be-
tween the terminal box
and the module is faulty.
The terminal box or the
module is defective.
No internal communica-
tion between the terminal
box and the module.
An R100 remote control
will indicate "Fault in
module communication".
The pump does not
The wires are not con-
react to the GENI-
nected correctly to the
bus signal.
terminal block.
The plug connection be-
tween the terminal box
and the module is faulty.
The terminal box or the
module is defective.
Remedy
Connect the wires cor-
rectly.
Correct the fault.
Replace the module.
Replace the terminal box.
Contact Grundfos.
Connect the wires cor-
rectly.
Correct the fault.
Replace the module.
Replace the terminal box.
Contact Grundfos.