Herunterladen Inhalt Inhalt Diese Seite drucken

Warning Label; Qualified Personnel; Product Introduction; Technical Data - LG RESU 16h Rrime Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1.3

Warning Label

Product/warning label and Battery Control Unit's traceability label are behind the front cover.
The front cover opens by turning the front cover handle counterclockwise. Battery Modules'
traceability labels are attached to the side of the Battery Modules.
Handle
Turn counterclockwise
1. Product/Warning Label
2. Traceability label
2-1. Battery Control Unit
2-2. Battery Module
EH257064P8S1DMA
○○○○○○○○○○
1.4 Qualifi ed Personnel
This guide for the tasks and procedures described herein is intended for use by skilled staff
only. A skilled staff is defi ned as a trained and qualifi ed electrician or installer who has all of
the following skills and experience:
• Knowledge of the functional principles and operation of on-grid and off -grid
(backup) systems
• Knowledge of the dangers and risks associated with installing and using electrical
devices and acceptable mitigation methods
• Knowledge of the installation of electrical devices
• Knowledge of and adherence to this guide and all safety precautions and best
practices
• Qualifi cation specifi ed in battery warranty fi le
: RESU-certifi cation in the battery website
: Knowledge of local installation standards
: Electrical license for battery installation required by the country or state
• Repair the battery by disassembly is possible only at the LG Service Center or by
a person who is specially authorized separately from the installation qualifi cation
4
1
2-1
2-2
2-2
SH128064P8S1BMA
SH128064P8S1BMA
○○○○○○○○○○A
○○○○○○○○○○B

2 Product Introduction

2.1 Technical Data

2.1.1

Dimensions and Weight

RESU16H Prime
Part Number
EH257064P8S1
Width
504 mm (19.8")
Height
1,086 mm (42.8")
Depth
295 mm (11.6")
Weight
159 kg (351 lbs)
1)
1) Battery pack weights may vary slightly.
2.1.2

Performance

Electrical Characteristics
Usable Energy
1)
Battery Capacity
Voltage Range
Absolute Max. Voltage
Max. Current (charging/discharging) 20A @ 350V
Max. Power (charging/discharging)
Peak Power
(only discharging)
2)
Peak Current (only discharging)
Communication Interface
DC Disconnect
Connection Method
User Interface
Operating Conditions
Installation Location
Operating Temperature
Operating Temperature
(Recommended)
Storage Temperature
Humidity
Altitude
Cooling Strategy
Certifi cation
Safety
Emissions
Hazardous Materials Classifi cation
Transportation
Ingress Rating
※ Test Conditions: Temperature 25°C/77°F, at the beginning of life.
※ Energy is measured under specifi c conditions from LG Energy Solution (0.3CPCV/0.3CP).
1) Value for battery pack only. Maximal usable energy at the AC output may vary by condition,
such as inverter effi ciency, confi guration and temperature.
2) Peak current excludes repeated short duration (less than 10 sec. of current pattern).
504 mm
(19.8")
16 kWh
64.1 Ah
350 to 450 VDC
595 VDC
7 kW
11 kW for 10 sec.
32.8A for 10 sec.
RS485/ CAN
Circuit Breaker
Spring Type Connector
LEDs for Normal and Fault Operation
Indoor/Outdoor (Standing Only)
charge
14°F to 122°F (-10°C to 50°C)
discharge
-4°F to 122°F (-20°C to 50°C)
59°F to 86°F (15°C to 30°C)
-22°F to 140°F (-30°C to 60°C), acceptable for 7
days in total
-4°F to 113°F (-20°C to 45°C), acceptable for the
fi rst 6 months
-4°F to 86°F (-20°C to 30°C), acceptable for months
7~12
5% to 95%
Max. 6,562 ft (2,000 m)
Natural Convection
Cell
UL1642
Battery
CE / RCM / IEC 62619 / UL1973 /
Pack
IEC62477-1
FCC
Class 9
UN38.3
IP55
1,086 mm
(42.8")
295 mm
(11.6")

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis