Herunterladen Inhalt Inhalt Diese Seite drucken

Carrier 40VL0058-7E-QEE Installations- Und Benutzerhandbuch Seite 29

Zwei-wege-konsole
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 93
Electrical Wiring
(B) Definition and description of SW03
SW03_1
Address setting
mode
Code-set indoor
SW03_2
unit address and
~
centralized
controller ad-
SW03_8
dress (Note*)
Note*:
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of the centralized controller=communication address+0 or +64.
SW03_ 2=OFF, address of the centralized controller=communication address+0=communication address
SW03_ 2=ON, address of the centralized controller=communication address+64 (applies when the centralized controller
is used and there are more than 64 indoor units).
• To use with 0010451181A in use, using code for address setting is required. Set SW03_1=0N
and SW03_ 2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7, and SW03_ 8 are address codes that are
set according to the actual address.
• The address-setting function of the wired controller for ultrathin card machines is disenabled.
Automatic address setting or wired controller address
[1]
0
1
[2]
[3]
[4]
[5]
[6]
[7]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
...
...
...
...
...
0
1
1
1
1
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
...
...
...
...
... ... ...
1
1
1
1
1
setting (default)
Code-set address
[8] Address of indoor unit
0
0
0# (Default)
0
1
1#
1
0
2#
...
...
...
1
1
63#
0
0
0#
0
1
1#
1
0
2#
...
1
1
63#
22
Address of centralized con-
troller
0# (Default)
1#
2#
...
63#
64#
65#
66#
...
127#

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis