Setting obstacle impact force sensitivity MOTOR 2
If the reaction time to obstacle impact force is too long, reduce the value of the parameter. If the impact
force exerted on obstacles is too high, reduce the value of parameter
(or
, if enabled:
different
from
)
Low motor torque:
01 = minimum obstacle impact force ... 10 = maximum obstacle impact force
N.B.: only use these settings if the medium motor torque values are not suitable for the installation.
Medium motor torque. Recommended setting for adjusting force settings correctly.
11 = minimum obstacle impact force ... 19 = maximum obstacle impact force.
Maximum motor torque. May only be used if the gate is equipped with a sensing edge.
Setting motor torque MOTOR 2
Increasing or decreasing the value of the parameter increases or decreases motor torque and, as a result,
adjusts obstacle detection sensitivity.
Use values below
SOLO
conditions (strong winds or very cold temperatures).
(reduced motor torque = increased sensitivity).
05= 0%.
06= +8%; 07= +16%; 08= +25%; 09= +35% (increased motor torque = reduced sensitivity).
The torque is set with parameter
.
Setting start acceleration MOTOR 1
Setting start acceleration MOTOR 2
01= the gate accelerates rapidly at start of manoeuvre.
...
05= the gate accelerates slowly and progressively at start of manoeuvre.
Enable electric lock release reverse impulse
Disabled.
Enabled. The controller applies a brief closing force (max. 4 s) to release the electric lock.
Enabling the lock release reverse impulse automatically enables the electric lock
=
.
Setting speed (%)
01= 60% minimum speed
...
05= 100% maximum speed.
Setting number of automatic closure attempts after activation of sensing edge
or obstacle detection (crush protection)
No automatic closure attempts.
From 1 to 3 automatic closure attempts.
We recommend setting a value equal to or lower than the value set for parameter
.
Automatic closure is only performed if the gate is completely open.
Setting photocell mode during gate opening (FT1)
DISABLED. Photocell is not active or not installed.
STOP. The gate stops and remains stationary until the next command is received.
when the photocell is cleared.
is cleared.
50