Safety Relay
Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.
The safety relay must be installed in switchgear cubicles complying
with degree of protection IP32, IP43 or IP54, depending on the prevailing
environmental conditions.
IMPORTANT NOTICE
The products described herein are designed to be components of a customized
machinery safety-oriented control system. A complete safety-oriented system
may include safety sensors, evaluators, actuators and signaling components. It
is the responsibility of each company to conduct its own evalution of the effec-
tiveness of the safety system by trained individuals. ABB AG, its subsidiaries
and affiliates (collectively "ABB") are not in a position to evaluate all of the cha-
racteristics of a given system or product or machine not designed by ABB.
ABB accepts no liability for any recommendation that may be implied or stated
herein. The warranty contained in the contract of sale by ABB is the sole war-
ranty of ABB. Any statements contained herein do not create new warranties or
modify existing ones.
Application
You can use the safety relay C572 in emergency tripping devices as per
DIN EN / IEC 60947-5-5, and in safety circuits as per DIN EN / IEC 60204-1, e.g.
with movable covers and guard doors.
Depending on the external circuit, max. Performance Level PL e / Cat. 4 accor-
ding to DIN EN ISO 13849-1 and/or SIL 3 according to DIN EN / IEC 62061 can
be achieved. The user must carry out an evaluation of the overall systems.
Functions and connections
Safety relay C572 has three release circuits which are configured as NO circuits
and two signaling cirucuits configured as an NC circuit. Three LEDs indicate ope-
rating state and function.
When the EMERGENCY OFF pushbutton or position switch is enabled and the ON
pushbutton is operated, the internal redundant safety relays, electronic circuitry
and external contactors are tested for proper functioning.
On the C572, the ON circuit Y33, Y34 is checked for short-circuit. This means
that a fault is detected when Y33, Y34 is closed before the emergency tripping
button is closed.
Operating
Terminal assignments
voltage
Only connect the PE terminal if ground
fault monitoring is required.
Output
Monitored
Monitored start/
Function
start
Autostart
Jumper from Y11 to Y12
Jumper from Y21 to Y22
1-channel
EMERGENCY OFF circuit at
ON
Y10, Y11
pushbutton at
Y33, Y34
Jumper from Y10 to Y11
2-channel
EMERGENCY OFF circuits at
Y11, Y12 and Y21, Y22
2
Cable lengths
for 2 x 1.5 mm
Figures Fig. I / II: Dimension drawings (dimensions in mm) / Installation
Fig. IIIa: Safety data
Fig. IIIb: Application data
2
A1
L/+
A2
N/
–
Observe notes
PE
on connection!
Fig. VIII
13, 14
Release circuit 1 (NO)
23, 24
Release circuit 2 (NO)
33, 34
Release circuit 3 (NO)
41, 42
Signaling circuit 1 (NC)
51, 52
Signaling circuit 2 (NC)
Autostart
Jumper or
feedback circuit
from Y33 to Y34
and jumper from
Y43 to Y44
max. 2000 m (total cable length for sensors)
Order No.: 2CDC 113 018 M9701
Figures Fig. IV: Internal circuit: ¿ power pack, À PTC fuse, Á control logic,
 Channel 1, à Channel 2
Autostart for guard door monitoring:
Fig. V:
1-channel
Fig. VI: 2-channel
Monitored start for emergency tripping:
Fig. VII: 1-channel
Fig. VIII: 2-channel
Fig. IX: grounding
Operation
LEDs
Operation
POWER Channel 1 Channel 2 PS
ON not activated was activated
Faults
• Relay fusion-welded
• Motor contactor fusion-welded
• Defect in electronics
• Short-circuit in ON circuit
Cross or ground faults in emergency
trip circuit (min. fault current
I
Kmin
Technical data
Permissible ambient temperature T
u
Operation / storage
Degree of protection to DIN EN / IEC 60529 IP20
Rated insulation voltage U
i
Rated impulse withstand voltage U
imp
Rated control supply voltage U
s
Rated power
AC / DC operating range
Shock resistance (half-sine) as per
DIN EN / IEC 60068
Weight
Recovery time after EMERGENCY STOP
Release time after EMERGENCY STOP
Pickup time, Monitored start
Pickup time, Autostart
Utilization category
Rated operational
voltage U
as per
(V)
DIN EN / IEC 60947-5-1
AC-15
230
DC-13
24
115
230
Continuous current I
th
Short-circuit protection Fuse links
for release circuit
Duty class
and signal circuit
Duty class
for enabling circuits and
Please adhere to the respective user information!
signaling circuits
(Order No.: C98130-A7524-A1-05-7419)
The safety relay is protected by an internal self-healing PTC fuse (multifuse).
Be sure to fit the specified fuses. Otherwise safe interruption
in the event of a fault cannot be guaranteed.
For further data and accessories see Catalog.
DIN EN / IEC 60947-5-1
English
Emergency
ON
trip
activated
not activated
not activated not activated
= 0.5 A; PTC fuse trips)
–25 to +60°C / –40 to +80°C
300 V
4 kV
24 V DC, 24 V AC, 115 V AC, 230 V AC
3 W
0.85 to 1.1 x U
s
8 g / 10 ms
460 g
min. 200 ms
max. 25 ms
max. 25 ms
max. 150 ms
Rated operational current I
with all release circuits loaded
e
(A)
60 °C
70 °C
6
4
6
4
0.2
0.2
0.1
0.1
6
4
DIAZED
gL (gG) 6 A / quick response 10 A
gL (gG) 6 A / quick response 6 A
C572
Release
circuits
closed
open
open
open
e