BTL7-A/C/E5 _ _ -M _ _ _ _ -SF-F _ _
Magnetostrictive Linear Position Sensor – Rod Style
6
Calibration procedure
Output
BTL
gradient
Rising
BTL7-A...
BTL7-C...
BTL7-E...
Falling
BTL7-A...
BTL7-C...
BTL7-E...
Tab. 6-1:
Value table for teach-in and inverting
6.1

Programming inputs

Programming inputs La and Lb must be used in order to
make settings. A programming input at 10 to 30 V
corresponds to activation (high active).
The Balluff calibration box BTL7-A-CB02-... can be used
for this (see Accessories on page 20).
Automatic deactivation!
If no signals are transmitted via the
programming inputs for approx. 10 min,
programming mode is automatically ended.
6.2

Calibration procedure notes

Prerequisites
Programming inputs are connected.
The BTL connected to the system controller.
Voltage or current values from the BTL can be read
(using a multimeter, the system control or the
calibration box).
Fig. 6-1:
Connecting the calibration box BTL7-A-CB02-S...
12
english
Unit
Min.
Null
value
value
V
–0.5
0
mA
0
0
mA
3.6
4.0
V
+10.5
+10.0
mA
20.4
20.0
mA
20.4
20.0
BTL
8-pin luster strip
Indication for
Indication
adjustment
for teach-in
2.0
4.0
6.0
12.0
6.0
12.0
2.0
4.0
6.0
12.0
6.0
12.0
Values for null and end point
Any desired position of the float can be used as the null
or end point. However, the null and end points may not
be reversed.
The absolute null and end points must lie within the
minimum or maximum range of what can be output
(see value table).
The last set values are always saved, regardless
of whether the setting was ended using the
programming inputs or automatically after
10 min. have expired.
Value table for teach-in and inverting
The following examples refer to BTLs with
0...10 V or 4...20 mA output.
Calibration box
YE
YE
8-pin
GY
GY
PK
PK
RD
RD
GN
GN
BU
BU
BN
BN
WH
WH
End
Max.
Error
value
value
value
+10.0
+10.5
+10.5
20.0
20.4
20.4
20.0
20.4
3.6
0
–0.5
–0.5
0
0
20.4
4.0
3.6
3.6
Supply
6-pin
Adapter cable with
connector (luster terminal)