Parameterization and Commissioning
EN
Status information display for the I/O module
EN
EN
EN
EN
EN
LCD display
EN
EN
slot
2:
module OK/mode:0
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
slot
1:
FW 02-04, HW 'E'
slot
3:
SNo: 123456-7890
20
CPU & power module
for Zone 2/Class I, Div. 2
Series 9440/15
The following displays show the same design for all I/O modules.
Display/function
Display of the slot, module type and module status.
AOM
Possible module statuses:
12268E00
Status information on the
LCD display
IOM no response
Hardware failure
conf unequal mod
HW disable outp.
prim. Rail fail
red. Rail fail
module OK/mode: x
In case of several faults, only the fault with the highest priority is displayed.
After eliminating this fault, the fault with the next highest priority is displayed.
Display of the firmware and hardware revision.
AOM
12269E00
Display of the serial number.
AOM
12270E00
Meaning
Communication with the module is not
possible. The module is defective or not
connected, or both BusRails and/or the
BusRail connecting cable are damaged
The module reports a hardware fault
Configuration error or the wrong
module was plugged in
Outputs disconnected by an external
switch (Plant-Stop)
(only with DOM 9475/2)
No communication via primary
BusRail data bus
No communication via redundant
BusRail data bus
Module is OK. No module error.
Signal errors are still possible.
The configured operating mode
(mode:x) is also displayed
Prio
1
2
3
4
5
5
6
162278 / 9440609310
2020-10-22·BA00·III·en·08