02.04
Rated voltage U
n
chained in V
(A.C.)
rms
200 - 230
380 - 480
500 - 600
660 - 690
Table 4.2
Settings of the parameter P071 on the SIMOVERT Master Drive as a function of the rated ac-side voltage
The following commissioning steps must be carried out after connecting the unit (as detailed in
Chapter 3):
♦ The rated ac-side voltage range must be set with the switch S500 (on board A23).
Unit order number
6SE70..-.EE85-0AA0
6SE70..-.FE85-0AA0
6SE70..-.HE85-0AA0
Table 4.3
Rated ac-side voltage ranges
♦ The start-up enabling status can be switched to the 'Warning' output (terminal X36) with the switch
jumper S1 (DIP-Fix). When S1 is open, the 'Warning' relay is opened only in the event of an excess
temperature prewarning.
Works setting:
S1 open
Close switch S501 only for flexible compliance (allowed only with increased prechokes)
Works setting and normal operation = open
♦ Switch on the mains and electronic power supply.
♦ Enable the converter.
Siemens AG
6SE7087-6AE85-0AA0
Common Rectifier
Operating instructions
dc link voltage range U
(DC) = 1,35 x U
n
(set parameter P071 = U
SIMOVERT Master Drive)
270 - 310
510 - 650
675 - 810
890 - 930
Rated ac-side voltage range
S500 closed
S500 open
AC (V)
200 - 230
380 - 480
500 - 600
660 - 690
in V
nd
on the
nd
Excess voltage
when
S500 closed
AC (V)
AC (V)
> 270
> 680
not intended
Start-up
Excess voltage
when
S500 open
AC (V)
> 548
not permitted
> 867
4-3
ENGLISH