9.11
Setting up process control and
executing P.LIN, P.TUNE
Configuration option:
Using the Bürkert Communicator PC software or the
display of the device (optional).
Display operation: Button functions
Select, activate
To set up process control, switch to the "Maintenance" detailed
view for process controllers.
How to switch to detailed view:
When using Bürkert Communicator for the configuration,
select
Process
Controller in the navigation area and switch
to MAINTENANCE.
When using the display for the configuration, switch to CON-
FIGURATION on the home screen, select Process Con-
troller and switch to MAINTENANCE.
You are now in the "Maintenance" detailed view.
9.11.1
Linearising process characteristic (P.LIN)
How to linearise the process characteristic:
Select CALIBRATION.
Select P.LIN.
The following text appears: "Do you really want to start P.LIN?"
Start P.LIN.
This will execute the P.LIN function.
40
Confirm
Back
English
Type 3360, 3361
Start-up
9.11.2 For devices without a display – activate
the correction characteristic
DIP switch 2, which is located under the blind cover, is used to
activate the correction characteristic.
To unlock the blind cover, turn it counterclockwise and
remove.
Set DIP switch 2 to ON. The correction characteristic is now
activated.
Unlock
blind cover
Figure 18: Activate correction characteristic
Close the blind cover.
9.11.3 Adjusting process control (P.TUNE)
How to trigger the P.TUNE function:
Select CALIBRATION.
Select P.TUNE. The following text appears: "Do you really
want to start P.TUNE?"
Start P.TUNE.
This will execute the P.TUNE function.
DIP switch
DIP 2  ON