7.4
Holding device
→
Attach the holding device to the pipe between the valve housing
and the actuator as shown in the picture.
In case of existing relief bore:
NOTE!
Make sure that the relief bore, which is used to detect leaks, is
not covered.
→
Fix the holding device in place by suitable means.
Figure 9: Mounting the holding device
22
8
The electromotive control valve is available with two connector
options:
• With a circular plug-in connector (multi-pin variant)
• Cable gland with connection terminals
Signal values
8.1
Relief bore
Risk of injury due to improper installation.
▶ Installation may be carried out by authorised technicians
▶ Observe general engineering standards & rules during
Risk of injury due to unintentional activation of the system
and uncontrolled restart.
Holding device
▶ Secure the system against unintentional activation.
▶ Following installation, ensure a controlled restart.
NOTE!
To ensure electromagnetic compatibility (EMC) the functional
earth must be connected to earth with a short line (max. 1 m).
Functional earth must have a cross-section of at least 1.5 mm².
English
Type 3360, 3361
Installing the valve
ELECTRICAL INSTALLATION
Operating voltage: 24 V
Set-point value: 0 ...20 mA; 4...20 mA, 0...5 V;
Electrical installation with circular
plug-in connector
WARNING!
only and with the appropriate tools.
installation.
0...10 V