Water Piping Installation of Air-Conditioning mode
Panasonic Air-to-Water
Heatpump Indoor Unit
Water
Water
Inlet
Outlet
External
Filter (Field Supply)
Water Piping Installation of TANK mode
Panasonic
Air-to-Water
Heatpump
Indoor Unit
Water Inlet
External Filter
(Field Supply)
B e sure to use two spanners to tighten the connection.
Tighten the nuts with torque wrench: 117.6 N•m {1176 kgf•cm}.
I f non-brass metallic piping is used for installation, make sure
to insulate the pipings to prevent galvanic corrosion.
M ake sure to insulate the water circuit pipings to prevent
reduction of heating capacity.
A fter installation, check the water leakage condition in
connection area during test run.
Water Outlet
Water Inlet
Insulation
M ount the PS foam
d
inlet and outlet connectors, as shown in below illustration.
PS Foam d
Water Connector
Long Banding Strap e
Space cooling can be achieved
through the fan coil unit ONLY.
High-spec Wired
Remote Controller
(CZ-RTC5)
2-way
Room Thermostat
Valve
(Field Supply)
Make sure to install
High-Spec Wired Remote
Controller (CZ-RTC5)
Water
Outlet
Tank Unit
CAUTION
Do not overtighten,
overtightening may cause
water leakage.
and long banding strap
e
PS Foam d
Water Connector

Expansion Vessel

E xpansion Vessel with 10 L air capacity and initial pressure of
1 bar is installed in this indoor unit.
T otal amount of water in system should be below 200 L.
(Note: This amount of water does not include the tank unit
volume)
Fan Coil Unit
I f total amount of water is over 200 L, please add expansion
vessel. (field supply)
P lease keep the installation height difference of system water
circuit within 10 m.
Radiator/Floor
(Inner volume of same indoor unit is about 5 L)
Heater

3-6. Indoor Unit Refrigerant Piping Installation

1. P lease make flare after inserting flare nut (located at joint
the 2-way Valve in
portion of tube assembly) onto the copper pipe. (In case of
case that radiator/
floor heater is
using long piping)
installed in the
2. D o not use pipe wrench to open refrigerant piping. Flare nut
cooling circuit.
may be broken and cause leakage. Use proper spanner or
ring wrench.
3. C onnect the piping:
A lign the centre of piping and sufficiently tighten the flare
nut with fingers.
F urther tighten the flare nut with torque wrench in
specified torque as stated in the table.
S-80MW1E5
S-125MW1E5
Do not overtighten, overtightening may cause gas leakage.

3-7. Drain Hose Installation

U se inner diameter 15 mm drain hose in the market.
T his hose must be installed in a continuously downward
direction and in a frost-free environment.
D o not insert this hose into sewage or drain hose that may
generate ammonia gas, sulfuric gas, etc.
I f necessary, use hose clamp to further tighten the hose at
drain hose connector to prevent leakage.
to water
W ater will drip from this hose, therefore the outlet of this hose
must be installed in an area where the outlet cannot become
blocked.
10
Piping size (Torque)
Model
Gas
ø15.88 mm (5/8")
65 N•m
{650 kgf•cm}
CAUTION
Gas Refrigerant Piping
Liquid Refrigerant Piping
Drain hose
connector
Drain hose
Drain water outlet
Liquid
ø9.52 mm (3/8")
42 N•m
{420 kgf•cm}