Unibox T RTL vario
12. Appendix
12.1 FAQs
QUESTION
Is it possible to connect two
heating circuits to the "Unibox
T RTL vario"?
How many m² of surface
temperature balance can I
connect to the "Unibox T RTL
vario"?
102273480-V01.07.2019
RESPONSE
Yes, use a "Duo connection piece" to connect two heating
circuits of the same size to one "Unibox T RTL vario". Each
surface temperature balance circuit may have a maximum pipe
length of 80 m, provided you use 16/17 mm pipes.
Illustr. 12: Connection diagram with two heating circuits using
"Duo connection piece"
You can connect a surface covering approximately 20 m² to
each "Unibox T RTL vario". The pipe length must not exceed
100 m when using a 17 mm pipe.