SHE Compact control panel EasyConnect 20A
10
Commissioning
Door display ready for operation
OK (green)
Door display mains 230 V (white)
Motherboard
F3
Test of SHE manual call point
Actuation
(red)
on the SHE manual call point
(black) on the SHE manual call point
Test of ventilation push button
Actuation
ventilation push button.
ventilation push button.
50
After the electrical connection of all external components
(24 V drives, SHE manual call points, automatic detectors,
24 V ventilation push button, wind/rain sensors, etc.) and the
line monitoring modules:
nals of the EasyConnect CP 20A (see
2 x 7-segment display
(see
The 230 V mains supply door display lights up white, the door
display OK (ready for operation OK) lights up green.
The 2 x 7-segment display of the motherboard shows i.O.
(OK). The SHE control panel is ready for operation.
Battery fuse F3
(yellow) FKS 20 A
CLOSED (0 position). If not, be sure to CLOSE them using
the connected ventilation push button.
Effect
SHE trip: Display F A on the 7-segment display of the motherboard.
The red LED on the SHE manual call point and in the housing door of the
control panel lights up. The green LED (operation OK) on the SHE manual
call point and in the housing door of the control panel lights up. The drive
output is switched (green LED above the drive terminals lights up). Drives
move to completely OPEN. Signalling contact 2 (trip) closed. Green LED
red).
Reset of the SHE trip.
Drives move to CLOSED (red LED above the drive terminals lights up).
The red LED on the SHE manual call point and in the housing door of the
control panel goes out. The green LED (operation OK) on the SHE manual
call point and in the housing door of the control panel lights up. Signalling
contact 2 (trip) open. After approx. 180 s, display I.O. on the 7-segment
display of the motherboard.
Effect
The drive output is switched (green LED above the drive terminals lights
up). Drives move to OPEN. The display "Ventilation OPEN" (Type LTA
25 only) lights up.
The drive output is switched (red LED above the drive terminals lights up).
Drives move to CLOSED. The display "Ventilation OPEN" (Type LTA 25
only) does not light up.
During this run, press STOP. (for Type LTA 12 STOP = press both buttons
OPEN and CLOSE together). The drives stop.
CLOSED. The display "Ventilation OPEN" (Type LTA 25 only) is not lit.
Note: The information on commissioning
refers to the standard functions.
All DIP switches are in the OFF position
Note: Before commissioning, check that the batteries
Operation without adequately secured batteries is not
permitted!
pages 10 + 11).
-
page 14, point
8.1).
-
01/13424999424