3.2.6 Measuring transducer
1:10
Below a dosing flow of 10 % no precise
Measuring range
measurement is possible. The current
signal 4 mA may probably not be
reached at a dosing flow of 0 %.
< ± 4 % from upper limit of the
Deviation of linearity
measuring range
4-20 mA
Current output
4 mA equals to 0 % dosing flow
20 mA equals to 100 % dosing flow
Power supply
24 V DC
Maximum load
600 Ω
Power consumption
> 0.5 W
Degree of protection
IP65
Degree of protection
0 °C to + 60 °C
3.2.7 Measurement and Control Electronics Conex
See operation manual of measuring amplifiers and controller
®
Conex
DIA-2Q or controller Conex

3.3 Dimensioned drawing

52,5
52,5
505
325
325
Fig. 15 Dimensional drawings of gas dosing systems VGS-141, VGS-143 and VGS-145
14
®
DIS-2Q.
610
390
30
375
45
50
450

Werbung