7. Description of program numbers
7.2 General settings
7.2.1 Running averaging
The total averaging time is given from the multiplication of the measuring time (PN14)
EN
and the registered averaging value (PN12). If one wants to see the running average on
the digital indicator, the display mode (PN15) must be programmed accordingly. This
must also be observed for the optional analogue output or with the switching outputs.
PN
Function
12
Averaging value
7.2.2 Refresh rate
The refresh rate determines how often the display values are updated. With strongly
fluctuating input signals, it is recommended that the refresh rate is adjusted (refresh rate
> 1s).
The refresh rate acts only on the presentation of the display values. Switching outputs
and other functions are not affected.
PN
Function
13
Refresh rate
28
Parameter
0 = off
1 ... 100 measured values
Parameter
0.1 ... 10.0 s (default 1 s)
WIKA operating instructions digital indicator, model DI35-M