Unbalanced connection (standard)
when using a single-shielded connection cable
Slot
Option/Connection option
IN 7
pH/ORP (redox) - Asymmetrical connection (standard)
IN 8
A separate temperature sensor can be connected to a temperature input or a universal input
IN 9
for temperature compensation.
IN 10
1 = glass/metal electrode (core) (A)
2 = not occupied
4 = bridge between 4 and 5
5 = bridge between 4 and 5
6 = reference electrode (inner shield) (B)
Balanced connection
(when using a double-shielded connection cable in conjunction with a separate earthing
pin in the liquid)
Slot
Option/Connection option
IN 7
pH/ORP (redox) - balanced connection
IN 8
serves to reduce interference by scattering electromagnetic fields along the sensor cable.
IN 9
A separate temperature sensor can be connected to a temperature input or a universal input
IN 10
for temperature compensation.
1 = glass/metal electrode (core) (A)
2 = not occupied
4 = reference electrode (inner shield) (B)
5 = liquid potential (earthing pin) (C)
6 = shield (outer shielding) (D)
Fig. 4: Anschlussbeispiel pH/ORP-(Redox)-Messung