Herunterladen Inhalt Inhalt Diese Seite drucken

O Box; Function; Input/Output Modules - Aventics HF03 Betriebsanleitung

Vorschau ausblenden Andere Handbücher für HF03:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
52
AVENTICS | HF03/HF02 | 1987765493–BDL–001–AB
System architecture
Plugs X1 to X8
Plug X10
Control elements
I/O modules on the
bus coupler
I/O modules on the
power module
3.1.3
Cannot be used in conjunction with I/O modules!
Connections for 32 inputs or outputs (inside the device)
Connections for voltage supplies (inside the device)
W
logic, 32 I/O box
W
outputs
W
inputs
Rotary switch for operating mode
Display
1 LED for each channel on the printed circuit board.
3.2
3.2.1
The input/output modules make it possible, via separable plug
connections, to control electrical input and output signals via
the valve system's bus connection.
A maximum of 12 input/output modules can be used
on one VS.
Observe the load limits!
The bus coupler supplies power to all I/O module inputs but only
the I/O module outputs that are lined up before a power module.
The maximum number of modules is also limited by the
maximum total current. This is 6 A for the outputs, 2 A for
the sensors.
The power module only supplies power to the outputs of the
I/O modules that are lined up after the power module.
The maximum number of modules is also limited by the
maximum total current. That is 12 A for the outputs.
The power module does not supply power to any inputs.
32 I/O box

Function

Input/output modules

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Hf02

Inhaltsverzeichnis