Assembly: Motor unit and electrical connection
Safety Instructions:
Caution! Any assembly work to the ventilation device may only be carried out after disconnecting all poles of the
supply voltage!
Make sure that the supply voltage of all connection lines is voltage-free (dead)! (Separation from the power supp-
ly with a minimum contact opening of 3 mm, e.g. electric fuse separating all poles).
Each electric circuit of this ventilation system must be fitted with a residual current protection (e.g. FI switch/
RCCB)!
Electric connection only by a specialist!
Additional installations and electrical components in this ventilation system are not admissible!
Slit the cable duct and tube (2 cm deep).
Only slit the tube vertically or horizontally!
Insert the mains cable (e.g. 3 x 1.5 mm²) at
an appropriate length into the tube.
Cover and insulate the mains cable as il-
lustrated. Lead it through the protective
sleeve of the motor and fix it with the cable
strain relief after the motor has been
connected to the mains (connection dia-
gram, see below). Screw the closure cap for
the electrical connection onto the motor.
Connection diagrams
N
L
30 m³/h continuous operation
60 m³/h with light switch
N
L
30 m³/h ON/OFF
horizontal
Only slit the tubes
in these four sec-
tions.
N
L
60 m³/h ON/OFF
EN
vertical
13