en
Configuration of integrated alarm devices
12.2 Green/Red strobe combination
12.2.1 Default setting: Horn active on A1 alarms
and on A2 alarms
Dip switch setting
1
2
ON
OFF
Default strobe and horn alarm pattern
Alarm conditions
A1
A2
System
fault
-
-
-
-
-
x
-
x
x
-
x
-
x
x
x
x
12.2.2 Setting: Horn only active on A2 alarms
Dip switch setting
1
2
ON
OFF
Strobe and horn alarm pattern
Alarm conditions
A1
A2
System
fault
-
-
-
-
-
x
-
x
x
-
x
-
x
x
x
x
26
Pins
3
4
ON
ON
ON/OFF
Strobes
Green
Red
-
-
x
-
-
-
-
x
-
-
-
x
-
-
-
x
-
Pins
3
4
OFF
ON
ON/OFF
Strobes
Green
Red
-
-
x
-
-
-
x
-
-
-
x
-
-
-
x
-
This combination does not indicate faults via the green
status light. If faults occur, the green status light stays on.
Settings within the menu are necessary, (see "Setting the
horn to only active on A2 alarms", page 26)
12.2.3 Setting the horn to only active on A2
alarms
5
This setting does not indicate faults via the green status light.
If faults occur, the green status light stays on.
This setting does not apply to instrument versions with
amber/red strobe combination.
To prevent the horn alarm at A1 alarms:
Horn
1. Open the instrument.
2. Toggle pins of the DIP switch.
-
1
-
ON
3. Configure the relay following the procedure in
11.2.1 Configuring relay A1 or A2.
a. Set the A1 relay to Energ. on alarm.
4. Configure the alarms following the procedure in
11.1 Alarm configuration.
a. Set the desired alarm thresholds for A1 and A2.
b. Set the same alarm direction and acknowledgment
settings for A1 and A2.
5. Close the instrument.
6. Commission the instrument.
5
Horn
-
-
-
-
Instructions for use
Pin
2
3
OFF
OFF
ON
|
Dräger PointGard 2000 Series
4
5
ON/OFF