3.5 Technical Safety Assembly Instructions
•
The appliance in which the filter is used must be free of limescale and gypsum deposits prior
to installation.
•
Protect the filter system from sunlight and mechanical damage. Do not assemble near
sources of heat and open flames.
•
A stop valve must be installed before the filter system inlet hose.
•
If the water pressure is greater than 8.6 bar, a pressure reducer must be installed in front of
the filter system.
•
When choosing the material for parts that come into contact with water after the BRITA filter
system, it is important to remember that, due to the process, decarbonised water contains
free carbon dioxide. For this reason, only materials that are compatible with free carbon dioxide
must be used. We recommend the use of BRITA hoses.
•
All parts must be installed in accordance with the country-specific guidelines on the installation
of drinking water facilities.
4 Installation
Caution: Prior to installation, read the technical data (Chapter 9) and the operating and safety
!
information (Chapter 3). After storage and transport below 0 °C, the product must be stored in
the open original packaging for at least 24 hours before it is commissioned at the stated ambient
temperatures (Chapter 9) for operation.
4.1 Assembling the filter head, water connection
•
Close the water intake and switch off the power supply to the end device
A
•
Fit the wall mounting bracket
Caution: When fitting the bracket, note the installation dimensions, bending radii of
!
B
the hoses and dimensions of the accessories (e.g. BRITA FlowMeter). When using the
wall mount, install vertically only! The PURITY C1100 cannot be installed using the wall
mounting bracket.
•
Fit the hoses to the water inlet "IN"
C
•
Use flat seals for G3/8" connections. For John Guest connections, use hoses with a diameter
of 8 mm. In the case of John Guest connections, the two safety clips
after fitting the hose.
Caution: The tightening torque at G3/8" connections must not exceed 14 Nm!
!
Only hose connections with flat seals may be used, as hoses with conical screw
connections damage the connections on the filter head and invalidate any warranty
claim! We recommend the use of BRITA hoses.
•
When using PURITY C 0–70 % filter heads, check by-pass setting
D
factory) and if necessary adjust this setting to the local carbonate hardness (PURITY C
Quell ST) and/or local total hardness (PURITY Finest C) (chapter 4.2).
•
Lock the filter head
4.2 By-pass setting for and capacity of PURITY C 0–70 % filter heads
•
Determine the carbonate hardness (for PURITY C Quell ST filter cartridges) or total hardness (for
PURITY Finest C filter cartridges) of the local water by performing the BRITA carbonate hardness
test or BRITA total hardness test. Alternatively, your local water supplier will be able to provide
information on the local water hardness.
•
Determine the by-pass setting and capacity in line with the application and the carbonate and/or
total hardness identified using the by-pass and capacity table (pages 2–6).
•
Then turn the by-pass setting
•
To ensure precise and continuous control of the degree of filter cartridge exhaustion, it is
recommended to install the BRITA FlowMeter 10–100 A.
•
Note: With PURITY C AC, PURITY Finest C and PURITY Fresh C filter cartridges, all of the
intake water is filtered. The filter cartridge can be used with filter heads that have a variable
or fixed by-pass. The by-pass that may be set in the filter head is not taken into account.
in the intended position
5
and outlet "OUT"
4
in the wall mounting bracket
1
to the identified value.
10
on the filter head
3
must be inserted
12
(set to 30 % at the
10
.
5
.
1
19