TECHNICAL DATA
TYPE
Thermal power – Output
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
Burner with CE marking in conformity with EEC directives: EMC89/336/EEC, Low Voltage 73/23/EEC,
Machines 98/37/EEC and Efficiency 92/42/EEC.
The burner meets protection level of IP 40, EN 60529 .
9
4
3
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air-damper
7 – Air-damper
8 – Combustion head adjustment screw
9 – Lock-out lamp and reset button
10 – Flange with insulating gaskets
2401
472T58
95 – 213 kW
–
Gas oil, viscosity 4 – 6 mm
Single phase, 220 V ± 10%
Run current 2.15 A – 3250 rpm – 340 rad/s
4 µ F
Secondary 8 kV – 16 mA
Pressure: 8 – 15 bar
0.4 kW
Fig. 1
7
6
6
10
D5399
BURNER EQUIPMENT
Quantity
2
1
4
1
1
1
1
GB
8 – 18 kg/h
2
/s at 20 °C
~
60Hz
2
Description
Flexible pipes with nipples
Flange with two insulating gaskets
Screws and nuts for flange
Screw with two nuts for flange
Cable grommet
Hinge (only for code 3747260)
ENGLISH
8
1
5