3AUA0000088632
•
Unfasten the insertion ramp and attach the LCL filter module to bottom plate.
•
Attach the drive module pedestal guide plate to the cabinet bottom plate.
•
Attach the telescopic insertion ramp to the pedestal guide plate.
•
Remove the sheeting from the clear plastic shrouds of the drive module from both
sides.
•
Install the top metallic shroud to the drive module.
•
Install the back shrouds to the drive module.
•
To prevent the drive module from falling, attach its lifting lugs with chains to the cabinet
frame.
•
Push the drive module carefully into the cabinet along the telescopic insertion ramp.
Work preferably with help from another person. Keep a constant pressure with one
foot on the base of the module to prevent the module from falling on its back.
•
Unfasten the insertion ramp and attach the drive module to the bottom plate.
•
Attach the LCL filter module and drive module to the punched section.
•
Attach LCL filter module to the drive module from top side. Reinstall the cover.
•
Connect the LCL filter busbars to the drive module busbars with the connecting
busbars.
•
Connect the LCL filter fan power supply cable to connector FAN3:LCL.
•
Connect the power cables and install the shrouds as described in section
the power cables and installing the
•
Install the external control unit and connect the control cables.
•
Install the air baffles.
Connecting the power cables and installing the shrouds
Step
1
Install the grounding terminal to the drive module base.
2
Run the motor cables to the cabinet. Ground the cable shields 360 degrees at the cabinet entry.
3
Connect the twisted shields of the motor cables to the grounding terminal.
EN – Quick installation guide 5
shrouds.
Task (motor cables)
EN
DA
DE
ES
FI
FR
IT
PL
PT
Connecting
RU
SV
TR
ZH