1. Introduction • The Master Controller, CF-MC, is a part of the new trend-setting CF wire- less hydronic floor heating control system from Danfoss. Based on -way wireless communication technology CF offers high transmission safety, easy wireless installation, a high level of individual room temperature control, and thus optimal comfort and improved energy efficiency.
Note: The relays for pump and boiler are potential free contacts and can thus NOT be used as direct power supply. Max. load is 230V and 8A / 2A (inductive) ! VI.UH.K2.80 Produced by Danfoss Floor Heating Hydronics 01.006...
Note #2: When the system is in cooling mode an independent dew-point alarm function should be installed. Danfoss offers the below listed components (see example fig. 17) EDA-4V: Electronic dew-point alarm - 088H001 EDA-S: Dew-point sensor - 088H011 TWA-A: 4V-NO actuator –...
Note: The Installation procedure of other system components to the Master Controller (Room Thermostats, Remote Controller, and Repeater Unit ; see 2.) is described in the enclosed instructions for these system components. Please see these instructions for specific installation procedures VI.UH.K2.80 Produced by Danfoss Floor Heating Hydronics 01.006...
Note: During periods with no output activations the Master Controller will run a valve motion program every 2 weeks and it will last for up to 12 minutes. Individual output configuration is possible with Remote Controller, CF-RC, see separate instruction. VI.UH.K2.80 Produced by Danfoss Floor Heating Hydronics 01.006...
Controller will switch to a fixed set room temperature at 8 °C for all Room Thermostats when the input for global standby is activated (fig. - (default) • Activate selected input configuration by pressing OK VI.UH.K2.80 Produced by Danfoss Floor Heating Hydronics 01.006...
• NO LEDs: The relays are not used (default) If local manifold and pump are separate: • 1 LED: Pump control • 4 LEDs: Pump control with min. start/stop delay • Activate selected relay configuration by pressing OK VI.UH.K2.80 Produced by Danfoss Floor Heating Hydronics 01.006...
• Release the push button when the red LED has been On and Off again • The Repeater Unit is now Reset and ready for installation to a Master Controller, CF-MC VI.UH.K2.80 Produced by Danfoss Floor Heating Hydronics 01.006...
* Buzzer is shut off by pressing OK. The error indication continues until the error is fixed ** If the Room Thermostat signal is lost, the Master Controller output will be activated 15 minutes every hour for frost protection until the error is fixed VI.UH.K2.80 Produced by Danfoss Floor Heating Hydronics 01.006...
Seite 13
6.4 Relais auf weiteren (-) Hauptregler............1 7. Ersetzen/Zurücksetzen des Hauptreglers ..........22 7.1 Wann? ........................ 7. Wie? ........................ 8. Technische Daten ..................23 9. Fehlersuche ....................23 10. Abbildungen ..................... A-B VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
Menü-LEDs Taste für Ausgangs- und Konfigurationsauswahl OK-Taste Ausgangs-LEDs Ausgangskabelbefestigung Relais für Pumpe und Heizung Eingang für Heizen/Kühlen (externer EIN/AUS-Schalter) Eingang für Standby (Absenkung auf 8 °C) (externer EIN/AUS- Schalter) Stromversorgung (0 V) VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
Anmerkung: Bei Verwendung von NC-Stellantrieben (NC = stromlos geschlos- sen) zur EIN-AUS-Reglung kann der Stellantrieb ohne Änderungen angeschlos- sen werden. Beim Einsatz von NO-Stellantrieben (NO = stromlos offen) muss der Ausgang konfiguriert werden (siehe 6.1). VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
• Befestigen Sie das Kabel (Fig. 14). Anmerkung: Der Standby-Betrieb stellt eine feste Raumtemperatur von 8 °C für alle Raumthermostate sicher. Diese Einstellung kann mit Hilfe der Fernbedie- nung CF-RC geändert werden. VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
Stellantrieben), sobald die Raumtemperatur den Sollwert überschreitet. Anmerkung Nr. 2: Wenn sich das System im Kühlmodus befindet, sollte ein un- abhängiger Taupunktmelder zur Taupunktüberwachung installiert werden. Danfoss bietet die folgenden Komponenten an (siehe Beispiel in Fig. 17). EDA-4 V: Elektronischer Taupunktmelder - 088H001 EDA-S: Taupunktfühler- 088H011 TWA-A: 4 V-NO-Stellantrieb –...
Funk-Verbindungstest verfahren wird. Raumthermostate: Wenn der Hauptregler das Testsignal (Verbindungstest) eines Raumther- mostaten empfängt, blinken die LED der zugeordneten Ausgänge. So können die Ausgänge identifiziert werden, die diesem Raumthermostat zugeordnet sind (Fig. - VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
Anmerkung: In Zeiträumen, in denen keine Ausgänge aktiviert werden, lässt der Hauptregler alle 2 Wochen für 12 Minuten ein Ventilbewegungs- programm ablaufen. Mit der Fernbedienung CF-RC, können die Ausgänge individuell konfiguriert werden, siehe separate Instruktion. VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
Hauptregler zu einer festen Raumtemperatur von 8 °C für alle Raumther- mostate, wenn der Eingang für Standby aktiviert wird (Fig. - (Standard). • Aktivieren Sie die gewählte Eingangskonfiguration, indem Sie auf OK drücken. VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
Wenn Verteiler und Umwälzpumpe nur für den jeweiligen Hauptregler verwendet wird: • 1 LED: Pumpenregelung • 4 LEDs: Pumpenregelung mit Min. Start-/Stoppverzögerung • Aktivieren Sie die gewählte Relaiskonfiguration, indem Sie auf OK drücken. VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
Sie die 0 V-Stromversorgung wieder her. • Lassen Sie den Druckschalter los, wenn die rote LED erloschen ist. • Der Signalverstärker ist jetzt zurückgesetzt und kann in einem Hauptregler CF-MC zugeordnet werden. VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
Fehler behoben ist. ** Wenn das Signal vom Raumthermostaten verloren geht, wird der Ausgang des Hauptreglers bis zur Behebung des Fehlers stündlich für 15 Minuten aktiviert, um Frostschutz zu gewährleisten. VI.UH.K2.80 Hergestellt von Danfoss Floor Heating Hydronics 01.006...
Seite 24
6.4 Relæer på flere (-) masterregulatorer ............ 1 7. Nulstilling af CF2 system ................32 7.1 Hvornår? ....................... 7. Hvordan? ...................... 8. Specifikationer .................... 33 9. Fejlfinding ....................33 10. Figurer og illustrationer ................A-B VI.UH.K2.80 Fremstillet af Danfoss Floor Heating Hydronics 01.006...
Vejledning CF-MC Masterregulator 1. Introduktion • Masterregulatoren CF-MC er en del af CF, Danfoss’ trådløse regulering af vandbåren gulvvarme. CF er baseret på trådløs teknologi til -vejskom- munikation, hvilket giver høj transmissionssikkerhed, let trådløs installa- tion og individuel styring af rumtemperatur.
Bemærk! Relæerne for pumpen og kedlen er potentialfri kontakter og kan således IKKE anvendes som direkte strømkilde. Maks. belastning er 230V og 8A/2A (induktiv)! VI.UH.K2.80 Fremstillet af Danfoss Floor Heating Hydronics 01.006...
0V stikkontakt. (fig. 18) Bemærk! Hvis strømstikket fjernes fra netledningen under installationen, skal man sikre, at tilslutningen sker i henhold til gældende regler/lovgivning. VI.UH.K2.80 Fremstillet af Danfoss Floor Heating Hydronics 01.006...
5.9 Andre systemkomponenter Bemærk! Installationsproceduren for andre systemkomponenter (rumtermo- stater, fjernbetjening og repeaterenhed, se afsnit 2) til masterregulatoren er beskrevet i de medfølgende vejledninger til disse systemkomponenter. Se disse vejledninger for de enkelte installationsprocedurer VI.UH.K2.80 Fremstillet af Danfoss Floor Heating Hydronics 01.006...
Bemærk! I perioder uden aktivering af udgangene kører masterregulatoren en aktivering af samtlige ventiler på op til 12 min. hver 14. dag. Individuel indstilling af udgange er mulig med fjernbetjeningen CF-RC, se separat vejledning. VI.UH.K2.80 Fremstillet af Danfoss Floor Heating Hydronics 01.006...
). I varmetilstand skifter masterregulatoren til en rumtemperatur på 8°C for alle rumtermostater, når indgangen for ) (standard) globalt standby aktiveres (fig. - • Tryk på OK for at aktivere den valgte indstilling. VI.UH.K2.80 Fremstillet af Danfoss Floor Heating Hydronics 01.006...
• INGEN indikatorer: Der anvendes ikke relæer (standard) Hvis lokal manifold og pumpe er separate: • 1 indikator: Pumperegulering • 4 indikatorer: Pumperegulering med min. start/stopforsinkelse • Tryk på OK for at aktivere den valgte konfiguration. VI.UH.K2.80 Fremstillet af Danfoss Floor Heating Hydronics 01.006...
• Slip knappen , når den røde indikator har været tændt og slukket igen • Repeaterenheden er nu nulstillet og klar til installation af en masterregulator af typen CF-MC VI.UH.K2.80 Fremstillet af Danfoss Floor Heating Hydronics 01.006...
* Buzzeren afbrydes ved tryk på OK. Fejlindikationen fortsætter, til fejlen er udbedret ** Hvis rumtermostatsignalet afbrydes, aktiveres masterregulatorens udgang i 15 minutter hver time som frostsikring, indtil fejlen er udbedret VI.UH.K2.80 Fremstillet af Danfoss Floor Heating Hydronics 01.006...
Seite 34
6.4 Relais sur Régulateurs principaux supplémentaires (-) ....41 7. Remplacer/Réintialiser le Réulateur principal ........42 7.1 Quand? ........................ 4 7. Comment? ......................4 8. Spécifications ....................43 9. Dépannage ....................43 10. Figures et illustrations ................A-B VI.UH.K2.80 Produit par Danfoss Floor Heating Hydronics 01.006...
• Le Régulateur principal CF-MC est un composant du nouveau système novateur de régulation du chauffage au sol hydronique sans fil CF de Danfoss. Basé sur la technologie de communication sans fil bidirection- nelle, le CF offre une sécurité de transmission élevée, une installation sans fil aisée, un haut niveau de régulation individuelle de la température...
à partir d’une alimentation électrique externe. S’assurer que l’alimentation électrique est déconnectée. Connecter ensuite le câble sous tension et effectuer les autres connexions à la chaudière selon les disposi- tions légales en vigueur. VI.UH.K2.80 Produit par Danfoss Floor Heating Hydronics 01.006...
Note No 2: Lorsque le système est en mode refroidissement, une fonction d’alarme point de condensation indépendante doit être installée. Danfoss propose les composants indiqués ci-dessous (voir exemple fig. 17) EDA-4V: Alarme électronique point de condensation - 088H001 EDA-S: Capteur point de condensation - 088H011 TWA-A: Actionneur NO-4V –...
• Déplacer le Régulateur principal No et/ou No si nécessaire. Le test de connexion sera initialisé automatiquement lors de la nouvelle connexion à l’alimentation électrique 0V VI.UH.K2.80 Produit par Danfoss Floor Heating Hydronics 01.006...
• diodes LED: Les sorties sont configurées pour des actionneurs NC avec régulation modulation en largeur d’impulsions (PWM) pour chauffage au • 4 diodes LED: Les sorties sont configurées pour des actionneurs NO avec régulation modulation en largeur d’impulsions (PWM) pour chauffage au VI.UH.K2.80 Produit par Danfoss Floor Heating Hydronics 01.006...
Sélectionner la configuration Entrée • Appuyer sur le bouton de sélection sortie et basculer entre les con- figurations Entrée possibles - les diodes LED de sortie seront allumées – indiqué ci-dessous: VI.UH.K2.80 Produit par Danfoss Floor Heating Hydronics 01.006...
Si le manifold local et la pompe sont séparés: • 1 diode LED: Commande pompe • 4 diodes LED: Commande pompe avec temporisation arrêt/marche de min. • Activer la configuration Relais sélectionnée en appuyant sur OK VI.UH.K2.80 Produit par Danfoss Floor Heating Hydronics 01.006...
• Relâcher le bouton poussoir , lorsque la diode LED rouge a été allumée et à nouveau éteinte • Le Réémetteur est maintenant réinitialisé et prêt pour l’installation à un Régulateur principal, CF-MC VI.UH.K2.80 Produit par Danfoss Floor Heating Hydronics 01.006...
** Si le signal du thermostat d’ambiance est perdu, la sortie du Régulateur principal sera activée 15 minutes toutes les heures comme protection contre le gel, jusqu’à ce que l’erreur soit éliminée VI.UH.K2.80 Produit par Danfoss Floor Heating Hydronics 01.006...
Seite 44
6.4 Reläer på flera (-) masterregulatorer ............51 7. Byte av masterregulatorn ................. 52 7.1 När? ......................... 5 7. Hur? ........................5 8. Specifikationer .................... 53 9. Felsökning ....................53 10. Bilder och illustrationer ................A-B VI.UH.K2.80 Tillverkad av Danfoss Floor Heating Hydronics 01.006...
Bruksanvisning CF-MC masterregulator 1. Introduktion • Masterregulatorn CF-MC utgör en del av CF, Danfoss trådlösa reglersys- tem för vattenburen golvvärme. CF baseras på trådlös teknologi för - vägskommunikation som ger hög transmissionssäkerhet och erbjuder en enkel trådlös installation och individuell styrning av rumstemperaturen.
Observera! Reläerna för pumpen och värmepannan är potentialfria kontakter och kan således INTE användas som direkt strömkälla. Den maximala belast- ningen är 230 V och 8 A/2 A (induktiv)! VI.UH.K2.80 Tillverkad av Danfoss Floor Heating Hydronics 01.006...
(ON vid NC-motorer/OFF vid NO-motorer) när rumstemperaturen överstiger referenspunkten. Observera 2! När systemet står i kylläge, bör ett oberoende daggpunktslarm installeras. Danfoss erbjuder nedanstående komponenter (se exempel på bild 17). EDA-4 V: elektroniskt daggpunktslarm - 088H001 EDA-S: daggpunktsgivare - 088H011 TWA-A: 4 V NO-termomotor – 088H111 RA-C 0: Danfoss kylventil* - 01G096 •...
Observera! Installationsprocessen för andra systemkomponenter för master- regulatorn (rumstermostater, fjärrkontroll och repeater-enhet, se avsnitt 2) finns beskriven i de medföljande bruksanvisningarna till respektive systemkom- ponent. För enskilda installationsprocesser, se de aktuella bruksanvisningarna. VI.UH.K2.80 Tillverkad av Danfoss Floor Heating Hydronics 01.006...
Observera! Under perioder utan aktivering av utgångarna kör masterregula- torn en aktivering av samtliga ventiler på upp till 12 minuter var 14:e dag. Individuell konfiguration av utgångarna är möjlig med hjälp av fjärrkontrollen CF-RC, se separat bruksanvisning. VI.UH.K2.80 Tillverkad av Danfoss Floor Heating Hydronics 01.006...
). I värmeläget växlar masterregulatorn över till en rumstemperatur på 8 °C för alla rumstermostater när ingången ) (standard). för överstyrning aktiveras (bild - • Tryck på OK för att aktivera den valda konfigurationen. VI.UH.K2.80 Tillverkad av Danfoss Floor Heating Hydronics 01.006...
• INGEN indikator: Inga reläer används (standard) Om lokal förgrening och pump är separata: • 1 indikator: pumpstyrning • 4 indikatorer: pumpstyrning med minuters start-/stoppfördröjning • Tryck på OK för att aktivera den valda konfigurationen. VI.UH.K2.80 Tillverkad av Danfoss Floor Heating Hydronics 01.006...
• Släpp knappen , när den röda indikatorn har tänts och sedan släckts igen. • Repeater-enheten har nu nollställts och är klar inför installation av en masterregulator av typen CF-MC. VI.UH.K2.80 Tillverkad av Danfoss Floor Heating Hydronics 01.006...
* Signalen bryts när du trycker på OK. Felindikationen fortsätter tills att felet har åtgärdats. ** Om rumstermostatssignalen bryts, aktiveras masterregulatorns utgång un- der 15 minuter varje timma som frostsäkring, tills att felet har åtgärdats. VI.UH.K2.80 Tillverkad av Danfoss Floor Heating Hydronics 01.006...