Attribute Name
PF
PhAng
Status Information
-
Settings
-
Tabelle 9: MMXU - Measurement
Attribute
Name
MMXU2
Common Logical Node Information
Mod
Beh
NamPlt
Controls
-
Measured values
TotW
TotVAr
TotVA
TotPF
Hz
PPV
PNV
A
W
16
TAPCON®
Attribute
Explanation
Type
WYE
Phase power factor
WYE
Phase Angle
-
-
-
-
5.1.8
MMXU2 - Measurement
Attribute
Explanation
Type
MMXU2
INC
Mode
ENS
Behaviour
LPL
Name plate
-
-
MV
Total active power (total P)
MV
Total reactive power (total Q)
MV
Total apparent power (total S)
MV
Average power factor (total PF)
MV
Frequency
DEL
Phase to phase voltages
(VL1VL2, ...)
WYE
Phase to neutral voltage
WYE
Phase currents (IL1, IL2, IL3)
WYE
Phase active power (P)
4077074/00 DE
5 Datenpunkte
M/O/E
Remarks
O
-
E
Unit: deg
Multiplier: none
-
-
-
-
M/O/E
Remarks
-
-
M
status-only
M
-
M
-
-
-
O
Unit: Watts
Multiplier: none
O
Unit: VAr
Multiplier: none
O
Unit: VA
Multiplier: none
O
-
O
Unit: Hz
Multiplier: none
O
Unit: V
Multiplier: none
E
Unit: V
Multiplier: none
O
Unit: A
Multiplier: none
O
Unit: Watts
Multiplier: none
Maschinenfabrik Reinhausen 2014