IDPlus 961-974 - HC
PAR. Description
Allows exclusion of the evaporator fans to be selected or not
selected during defrost.
dFd
n (0) = no (depending on parameter FCO);
y (1) = yes (fan excluded).
Selects or deselects fan deactivation at compressor OFF.
FCO
0 = fans off; 1 = thermostat-controlled fans; 2 = duty cycle.
Fon Time fans remain ON during daytime duty cycle.
FoF Time fans remain OFF during daytime duty cycle.
Fnn Time fans remain ON during night-time duty cycle.
FnF Time fans remain OFF during night-time duty cycle.
ESF "Night" activation mode. n (0) = no; y (1) = yes.
ALARMS (folder "AL")
Can be used to select absolute (Att=0) or relative (Att=1)
Att
values for HAL and LAL parameters.
AFd Alarm differential.
HAL Maximum temperature alarm.
LAL Minimum temperature alarm.
PAO Alarm exclusion time on switching back on after power outage.
dAO Temperature alarm exclusion time after defrost.
OAO Alarm signaling delay after digital input disabling.
tdO Door open alarm activation delay.
tAO Delay preceding temperature alarm signal.
9IS54671.00 10 - 2018
Range
UM
AP1 AP2 AP3 AP4
n/y
flag
y
0/1/2
num
0
0...99
min
0
0...99
min
0
0...99
min
0
0...99
min
0
n/y
flag
n
0/1
flag
0
1.0...50.0 °C/°F 2.0
LAL...302 °C/°F 50.0 50.0 50.0 50.0
-58.0...HAL °C/°F -50.0 -50.0 -50.0 -50.0
0...10
hours
0
0...999
min
0
0...10
hours
0
0...250
min
0
0...250
min
0