ABB 2600T-Serie Bedienungsanleitung Seite 12

Engineered solutions for all applications
Vorschau ausblenden Andere Handbücher für 2600T-Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4.6.2 PROFIBUS PA
There are 3 dip switches located on this kind of secondary
electronics (as indicated by the figure); they are used for
settings when integral display is not available.
Switch 1 and 2 allow the REPLACE MODE for sensor or
secondary electronics.
Switch 3 identifies the external push buttons functionalities:
Zero/Span adjustments or PV Bias-Offset / PV Bias Reset.
The electronic label clearly explains how to perform all the
possible selection, but please remember that all the operations
with the dip switches should be carried out when the
transmitter is powered off so as to upload new configurations
at instrument start-up.
Replace mode (switch 1 and 2)
Usually switches 1 and 2 are down in "0" position.
They are moved when a replace operation is required.
Switch 1 up in "1" position is required before power up the
transmitter, when user needs to replace the electronics or the
sensor.
Switch 2 down in "0" position allows the replace of the
secondary electronics. It must be moved in this position before
power up the transmitter.
Switch 2 up in "1" position indicates that a new sensor has
been installed.
AFTER ANY REPLACE OPERATION IT IS RECOMMENDED TO
MOVE DOWN IN "0" POSITION THE RELEVANT SWITCHES.
Push buttons mode (switch 3)
Dip switch 3 is set at the factory on "0" position. This means
that the external push buttons perform the zero/span
adjustments. If the user puts this switch on "1" position, the
zero push buttons will modify the PV Bias-Offset and the span
push button will reset the PV Bias-Offset value.
4.6.3 FOUNDATION Fieldbus
There are 4 dip switches located on this kind of secondary
electronics (as indicated by the figure); they are used for
settings when integral display is not available.
Switch 1 and 2 allow the REPLACE MODE for sensor or
secondary electronics.
Switch 3 identifies the external push buttons functionalities:
Zero/Span adjustments or PV Bias-Offset / PV Bias Reset.
Switch 4 for performing the Simulation mode. The electronic
label clearly explains how to perform all the possible selection,
but please remember that all the operations with the dip
switches should be carried out when the transmitter is powered
off so as to upload new configurations at instrument start-up.
Replace mode (switch 1 and 2)
Usually switches 1 and 2 are down in "0" position.They are
moved when a replace operation is required. Switch 1 up in "1"
position is required before power up the transmitter, when user
needs to replace the electronics or the sensor.
Switch 2 down in "0" position allows the replace of the
secondary electronics. It must be moved in this position before
12 SOI/266-XC Rev. D | 2600T Series Pressure transmitters
power up the transmitter. Switch 2 up in "1" position indicates
that a new sensor has been installed.
AFTER ANY REPLACE OPERATION IT IS RECOMMENDED TO
MOVE DOWN IN "0" POSITION THE RELEVANT SWITCHES.
Push buttons mode (switch 3)
Dip switch 3 is set at the factory on "0" position. This means
that the external push buttons perform the zero/span
adjustments. If the user puts this switch on "1" position, the
zero push buttons will modify the PV Bias-Offset and the span
push button will reset the PV Bias-Offset value.
Simulation mode (switch 4)
Dip switch 4 in "1" position enables the Simulation mode. This
feature is available in order to initialize all the parameters
requiring a well defined value, with the default values congruent
to the connected sensor type/model. This operation can be
performed before powering on the device. Many variables of
the AI and TPB are properly set with values strictly related to
the connected transducer type.
4.7 Easy set-up
The easy set-up procedure is made possible thanks to the
intuitive HMI, connected on the transmitter communication
board. To navigate the 266 HMI please follow the various
indications that will appear on the bottom of the display.
To facilitate commissioning the 266 HMI has the capability to
run a sequence of predefined setup steps with the main
configuration settings. When you start the Easy Setup you must
continue up to the end to exit.
4.7.1 To start the Easy Set-up
Navigate the Digital LCD Integral Display menu, push the
button on the right under the LCD display.
4.7.2 Define the language
If the desired language is different from the indicated language
select Edit then scroll the desired language (see the following
table) with the up and down keys and confirm with OK. Select
Next to continue.
English
German
4.7.3 Insert tag
If the Tag number of the instrument is different from the value
set in the factory, use this part of the easy set-up menu to
change it.
4 Transmitter configuration