Wiring a version with double
inductive 4-wire switch
Orange light (valve open detection)
Green light
(voltage
Red light (valve closed detection)
present)
S01
4
S02
3
0V
S01
2
V+ 1
S02
Fig. 17: Wiring the 2 outputs of a version with a double inductive
4-wire switch, in PNP mode, valve open detection (output
S01) and/or valve closed detection (output S02)
34
Load 2
Reaction speed
150 mA max.
according to the
max. load
500 mA
+
10-30 VDC
-
Power supply
+ -
150 mA max.
Load 1
english
Type 1062

Commissioning

9
commissioninG
9.1

safety instructions

Warning
Danger due to nonconforming commissioning.
Nonconforming commissioning could lead to injuries and damage
the device and its surroundings.
▶ Before commissioning, make sure that the staff in charge have
read and fully understood the contents of the manual.
▶ In particular, observe the safety recommendations and intended
use.
▶ The device/installation must only be commissioned by suitably
trained staff.
▶ Protect the device against electromagnetic interference and
ultraviolet rays.
protect this device against electromagnetic inter-
ference, ultraviolet rays and, when installed outdoors,
the effects of climatic conditions.
9.2

setting the cams

Activate the valve to check the correct detection of the open and/or
closed position.
If detection is incorrect, reposition each cam opposite its switch
according to the position of the valve as shown in the photos in „Fig.
17".