Parameterizing Steps
9.1

Parameter reset to factory setting

NOTE
P053 = 27 hex
P060 = 2
P366 = 0
P970 = 0
Unit carries out parameter
reset and then leaves the
"Fixed settings" menu
9-2
The factory setting is the defined initial state of all parameters of a unit.
The units are delivered with this setting.
You can restore this initial state at any time by resetting the parameters
to the factory setting, thus canceling all parameter changes made since
the unit was delivered.
The parameters for defining the power section and for releasing the
technology options and the operating hours counter and fault memory
are not changed by a parameter reset to factory setting.
Parameter number
P070
P072
P073
P366
Table 9-1
Parameters which are not changed by the factory setting
Parameter factory settings which are dependent on converter or motor
parameters are marked with '(~)' in the block diagrams.
Grant parameter access
27 hex: Changing parameters is permitted via PMU, serial
interface SCom1 / SCom2 (OP1S) and
Communication Board (e.g. CBP2 - PROFIBUS).
Select "Fixed settings" menu
Select desired factory setting
0: Standard with PMU, setpoint via MOP (BICO1)
Start parameter reset
0: Parameter reset
1: No parameter change
Fig. 9-2
Sequence for parameter reset to factory setting
Parameter name
Order No. 6SE70..
Rtd Drive Amps
Rtd Drive Power
Select FactSet
6SE7087-6JP60
Operating Instructions
SIMOVERT MASTERDRIVES
05.2003
Siemens AG