Herunterladen Inhalt Inhalt Diese Seite drucken

Initial Setup And Start; User Interface; Operating Modes - SMA SUNNY TRIPOWER STORAGE 60 Installationsanleitung

Vorschau ausblenden Andere Handbücher für SUNNY TRIPOWER STORAGE 60:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 47
3  Initial Setup and Start

3 Initial Setup and Start

3.1 User interface

The user interface comprises:
• Local display, for all inverter variants. The local display
shows status information of the inverter. It is not
possible to set up or configure the inverter via the
display. The "#" in the display explains the operation
modes.
• Local commissioning and service tool (LCS-Tool). The
LCS tool can be used for configuring one or more
inverters.

3.1.1 Operating modes

The inverter has five operation modes, indicated by LEDs.
Status
Off grid
Connecting
On grid
Internal inverter event
Fail safe
Table 3.1 Operating modes
Off grid (LEDs off)
#0-51
Under certain operating conditions, the inverter disconnects
from the grid and shuts down. User and communication
interfaces remain powered for communication purposes.
Connecting (green LED flashing)
#52-53
Once the DC input voltage reaches the DC initial voltage,
the inverter goes into operation. The inverter performs a
series of internal self-tests, including measurement of the
resistance between the DC side and ground. Meanwhile, it
also monitors the grid parameters. If the grid parameters are
within the specifications during the required period
30
STPS60-IA-xx-12
LEDs
LEDs
Green
Red
Green
Red
Green
Red
Green
Red
Green
Red
(depending on the grid code) and in accordance with local
standards and directives, the inverter starts operating on the
utility grid.
On grid (green LED glowing)
#60
The inverter is connected to the AC grid and feeds into the
grid. The inverter disconnects from the utility grid in the
following cases:
• The inverter recognizes abnormal grid conditions
(depending on the grid code).
• An internal event occurs.
• Due to operating conditions.
Internal inverter event (green LED flashing)
#54
The inverter waits for an internal state within the thresholds
(e.g. due to too high a temperature) before reconnecting to
the utility grid.
Fail safe (red LED flashing)
#70
If the inverter detects an error in its circuits during the self-test
(in the "Connecting" operating mode) or during operation,
it switches over to the "Fail safe" operating mode and is
disconnected from the utility grid. The inverter remains in the
"Fail safe" operating mode until the DC power has been
absent for ten minutes or the inverter has been shut down
completely (AC+DC).
SMA Solar Technology AG
Installation Manual

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis