Application
The JRGURED UP pressure reducer is approved for the following parameters:
JRG Code
1380.320
1'600 kPa (16 bar)
* Temperatures up to 90°C are permissible for short periods during thermal disinfection
Designation
- ¾ (GN/valve size)
- JRG (manufacturer)
- u (flow direction arrows)
Factory settings
The pressure reducer JRGURED UP is factory-set to 300 kPa (3 bar) static pressure.
Installation instructions
Thoroughly flush the supply line before installing the JRGURED UP cartridge and
commissioning the pressure reducer.
PN
P
sec
250-450 kPa (2.5-4.5 bar)
E
t
*
max
70°C