LIFT EMERGENCY TELEPHONES
Distance of the loudspeaker, microphone and buttons from the basic unit: 25 m max.
Buttons must not have a common return wire. To connect the basic electronics package with the user-interface
elements (loudspeaker, microphone and buttons) a shielded cable must be used. IY-ST-Y or AY-ST-Y. Connect
shield to –12 V terminal (see also Seite 2). Mount dial pad at a distance of 25 m max. (use Behnke patch cable
for connecting the dial pad).
In order to connect MLM A to C (microphone/loudspeaker modules = user units comprising loudspeaker, micro-
phone and button), you should use original Behnke patch cables – see also page 10.
The integrated add-on amplifier (1 W) can only be activated for MLM A. The corresponding configuration steps can
be found in our comprehensive technical manual (available as PDF on the Internet – see also note on page 2).
Additional power supply
provided by BNOS UPS (only
Connect shield for
required for special functions)
microphone and
buttons to –12 V,
not to earth!
0.5 A 120 V AC or 1 A 24 V DC
0.5 A 120 V AC or 1 A 24 V DC
Standard = 'make
contact'; if button
is to be used as a
Make or break contacts may
'break contact', the
be used as nonlocking buttons
configuration must
be changed (see
comprehensive
technical manual;
available as PDF on
inside the car must be
the Internet).
Main board
Earth
Telephone line
analogue direct exchange
line or PBX extension.
a wire
b wire
potential-free voltage, e.g.
–
12 V DC=
+
Relay 1
Relay contact rating:
60 VA 24 W max.
NC
Com.
NO
Relay 2
Relay contact rating:
60 VA 24 W max.
NC
Com.
NO
Alarm input
Alarm condition is
active while voltage is
applied
–
6 to 24 V DC=
+
Buttons
T1 button
Common contact
T2 button
Note: The button
connected to the T2
terminal.
Telefonbau Behnke GmbH
1
2
3
4
6
7
8
9
T1
MLM A
T2
+MLM C
+MLM B
− MIC +
LS
− MIC +
LS
red
blue
yellow
yellow
blue
red
Note:
The board's connectors are labelled in German:
While MLM and LS have the same meaning as
in English (i.e. microphone/loudspeaker module
and loudspeaker), T1 and T2 refer to button 1 and
button 2 (German 'Taste').
Connector for
electronics extensions
featuring a voice-
announcement facility,
a clock or a display
EEPROM
Master processor
Internal
5
∗
configuration and
∗
dialling keyboard
#
0
#
T
Telephone 'ON'
E
L
Connection board
1
2
3
\
4
5
6
\
7
8
9 i
0
# +
*
Dial pad
Loudspeaker
Microphone
+
–
MLM A
= main MLM
inside the car
Program phone number
with configuration step 22
MLM B
= additional MLM
on top of the car
Program phone number
with configuration step 23
MLM C
= additional MLM
under the car
Program phone number
with configuration step 24
17