PE terminal
1. Connect the PE terminal (M4 thread)
the device with large-area contact to the
equipotential bonding line. The minimum
cross-section of the equipotential bonding
line is 2.5 mm
.
2
2. Connect the equipotential bonding line with
large-area contact to the protective ground
conductor of the cabinet or the plant in
which the device is to be installed.
5.2
Connecting the 24 V DC power supply
To be noted before you connect the device
Note the following in order to operate the device safely and according to regulation:
WARNING
The device should only be connected to a 24V DC power supply which satisfies the requirements of safe extra low voltage
(SELV).
If the device is used on a wall, in an open rack or other similar locations, an NEC Class 2 current source is required in
order to meet the UL requirements (UL 60950-1). In all other cases (IEC / EN / DIN EN 60950-1) either a current source of
limited output (LPS = Low Power Source), or a line-side fuse or a line-side circuit breaker is necessary. The power needs
to be limited to a value below 4.16 A. The fuse value required: Max. 4 A.
Use the special plug supplied to connect the supply voltage.
Note
The permitted cable cross-section for the 24 VDC connection is 0.75 mm
Connecting
Steps for connecting the device to the 24 V DC power supply
1.
Switch off the 24 VDC power source
2.
Connect the power supply via the connector (when
shipped, the connector is inserted in the socket)
22
on
to 2.5 mm
.
2
2
SCALANCE WLC711
A5E03740572-05, 04/2016