Herunterladen Inhalt Inhalt Diese Seite drucken

LEGRAND Megaline Rack Benutzeranleitung Seite 45

Vorschau ausblenden Andere Handbücher für Megaline Rack:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 81
SIMPLE MODE
Batteries
ð
Set capacity
Battery Thresholds
Batteries
Max Time On Batt.
Max time reserve
ð
TurnOn Test Enable
Restart Enable
External options
Set capacity
Simple mode
Sets the warning signal for the end of battery
autonomy using the battery voltage.
There are two possible settings in the
Mode menu
If you select
Mode – Automatic thresholds
The UPS automatically calculates the voltage
thresholds based on the load: the UPS will signal
AUTONOMY RESERVE and END OF AUTONOMY,
respectively, below these.
Battery
Thresholds
If you select
Mode – Fixed thresholds
There are two options for this setting:
1) Reserve threshold
Sets the battery voltage threshold; the UPS will signal
AUTONOMY RESERVE below this
2) Exhaust threshold.
Sets the battery voltage threshold; the UPS will signal
END OF AUTONOMY below this.
Sets the maximum time for continuous operation
Max Time
in BATTERY mode, shown in seconds.
On Batt.
If "0" is set, this function is disabled.
Sets the maximum time for operation in BATTERY
Max time
mode after the reserve limit has been reached,
reserve
shown in seconds. If "0" is set, this function is disabled.
If enabled, the batteries are tested each time
TurnOn Test
the UPS is switched on. If disabled, the batteries
Enable
are not tested when it is switched on again.
If enabled, the UPS will switch on again when mains
power is restored after switching off due to the end of its
Restart
autonomy. If disabled, the UPS will not switch back on
Enable
when mains power is restored after switching off due to
the end of its autonomy.
Battery Chargers N°
Sets the number of external battery chargers
External
KB Units
options
Sets the number of packs of three batteries fitted
externally
Megaline Rack
45

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis