Connecting devices
Connecting an additional AMC device:
-
You can provide each device with an individual power supply, or
pass power through from one device to the next:
-
NOTICE!
In general:
-
i
-
CAUTION!
!
Do not create any ground loops.
NOTICE!
i
When connecting devices please consult the instructions and
notices in their respective installation manual.
F.01U.097.256 | V 1.1 | 2008.12
Connect the RS485 slave interface of the second AMC
device to the RS485 slave interface of the AMC2 marked
RS-485EXT.
If a second device receives its power supply from a first,
then please connect the power lines (pin 1 and pin 2) as
well as the data lines (pin 3 and pin 6).
If the devices have their own power supplies then the
cable shielding should be grounded at one end only. The
loose end should be insulated to prevent any inadvertent
contact.
If one device passes power through to another, then the
cable shielding should be grounded at both ends.