Configuration and Parameterization

6.3.5 Scaling parameter PNO CLASS 2

If the scaling parameters are activated with the Scaling function, the physical
resolution of the measuring system can be changed. The position value output is
binary decoded and is calculated with a zero point correction and the count direction
set. The measuring system does not support decimal numbers in this configuration or
numbers of revolutions (gearbox function) deviating from exponents of 2.

6.3.5.1 Measuring units per revolution

Defines how many steps the measuring system outputs for one revolution of the
measuring system shaft.
Lower limit
Upper limit
Default

6.3.5.2 Total measuring range / units

Defines the total number of steps of the measuring system before the measuring
system restarts at zero.
Lower limit
Upper limit PNO CLASS 2 16 bit
Upper limit PNO CLASS 2 32 bit
Default
The actual upper limit for the measurement length to be entered in steps is dependent
on the measuring system version and can be calculated with the formula below. As
the value "0" is already counted as a step, the end value = measurement length in
steps - 1.
To calculate, the parameters steps/rev. and the number of revolutions can be read
on the measuring system nameplate.
 TR-Electronic GmbH 2016, All Rights Reserved
Page 82 of 103
1 step / revolution
8192 steps per revolution (Max. value see nameplate)
4096
Total measuring range = Steps per revolution * Number of revolutions
TR - ECE - BA - DGB - 0131 - 02
16 steps
65 536 steps
33 554 432 steps (25 bit)
4096
Printed in the Federal Republic of Germany
10/31/2018