Flow switch HFS 2100 with ATEX approval
5

Electrical connection

The switching contacts used in the instruments are potential free and do not need any
supply.
Attention!
Switching contact and unit are matched. After the exchange of a switching contact
a readjustment must be made.
Kindly request the relevant instruction.
5.1

Standard switching contacts

Normally
Open
(SEM-E)
2
1
5.2

Contact protection arrangement

The switch unit may only be connected to circuits with the following maximum ratings:
Change-over contact (SEM-A):
Normally open contact (SEM-E): U
The circuit must not incorporate any effective inductivities or effective capacities. Above
mentioned max. ratings must never be exceeded. For contact protection a fuse with the
nominal value of 1 A (Change-over contact) respectively 2 A (Normally open contact) must
be provided outside of the Hazardous Area for the circuit, unless the switch unit is
connected to an intrinsic safe circuit.
Status 2012/09/18
Change-
over
(SEM-A)
2
3
1
U
= 250 V / I
max
= 250 V / I
max
HYDAC ELECTRONIC GMBH
= 1 A / P
= 30 W
max
max
= 2 A / P
= 60 W
max
max
Page 9