4. Select measurement units (P005)
meters
1
*
centimeters
2
millimeters
Value
3
feet
4
inches
5
5. Set process empty level (P006: Empty)
P006 and P007 are interlinked: see
Note:
notes attached to P007.
Range 0.0000 to 20.00
Value
Default 20.00 m (max. range)
Empty can be set to any distance: not
necessarily the bottom of the tank.
reference
point
Span
(100% Level)
P006
P007
Level
Empty
6. Set measurement range (P007: Span)
Range
Value
Default
Span can be set at any distance above
Empty level.
1.
Default setting for Blanking is 0.4 m
7ML19985QL83
1
Distance
Space
(0% Level)
0.0000 to 20.00
19.56 m (see note
below)
SITRANS LR200 (HART) – QUICK START MANUAL
.
Notes:
• Setting P006 resets Span, if it has not
previously been set to a different value.
• The default setting for Span is based
on Operation (P001) and Empty (P006).
Span is set to Empty minus 110% of
Blanking distance
set to distance (P001=3). In this case,
Span is set to Empty distance.
• Always prevent the monitored surface
from approaching within 0.3 m (1 ft) of
the reference point, as this is the
minimum distance detectable.
7. Minimize false reflections: Set P838
(Auto False Echo Suppression
Distance)
Use P837 and P838 together: see next page
for step-by-step instructions.
Range: 0.0000 to 20.00 (m)
Value
1.000
*
8. Enable False Echo Suppression: set
P837 (Auto False Echo Suppression.
Off
0
Use "learned" TVT
Value
1
*
"Learn"
2
1
unless Operation is
Page EN-17