1
Introduction
This installation guide describes basic concepts about Division 2 hazardous areas and
provides installation guidelines for installing the Factory Mutual approved PANTHER
panel-mount terminal into hazardous environments rated as Division 2. Only PANTHER
panel-mount terminals which are factory-labeled as approved for Division 2 may be
installed into Division 2 hazardous areas. Refer to the next chapter for details of the
required data plate markings. Previous models of the PANTHER terminal which are not
factory-labeled for Division 2 compliance may not be installed into Division 2
environments. The PANTHER harsh environment terminal is NOT approved for use in
areas classified as Division 2.
Only analog load cell versions of the PANTHER panel-mount terminal have bee
approved for use in a Division 2 area. DigiTOL versions of the PANTHER panel-mount
terminal are NOT approved for use in areas classified as Division 2.
METTLER TOLEDO ASSUMES NO RESPONSIBILITY FOR CORRECT
INSTALLATION OF THIS EQUIPMENT WITHIN A DIVISION 2 AREA.
THE INSTALLER MUST BE FAMILIAR WITH ALL DIVISION 2 WIRING
AND INSTALLATION REQUIREMENTS.
At the end of this guide, there is a METTLER TOLEDO control drawing number 155907R.
The PANTHER panel-mount terminal must be installed according to this control drawing.
No exceptions are permitted. In addition, the installer must be familiar with all other
wiring and installation requirements for Division 2 areas.
IN ORDER TO USE THE ANALOG PANTHER PANEL-MOUNT
TERMINAL IN AN AREA CLASSIFIED AS CLASS I, II OR III, DIVISION
2, GROUPS A, B, C, D, F OR G, METTLER TOLEDO CONTROL
DRAWING 155907R MUST BE FOLLOWED WITHOUT EXCEPTION.
FAILURE TO DO SO COULD RESULT IN BODILY HARM AND/OR
PROPERTY DAMAGE.
The PANTHER panel-mount terminal has been approved for use in an area classified as
Division 2. This approval DOES NOT mean that the PANTHER panel-mount terminal
can be used in Division 1 areas. Different precautions must be taken when installing
equipment into a Division 1 area. Please consult your local METTLER TOLEDO
representative regarding applications in a Division 1 area.
THE PANTHER PANEL-MOUNT TERMINAL IS NOT INTRINSICALLY
SAFE! DO NOT USE WITHIN AREAS CLASSIFIED AS HAZARDOUS
DIVISION 1 OR ZONE 0/1 BECAUSE OF COMBUSTIBLE OR
EXPLOSIVE ATMOSPHERES.
Chapter 1: Introduction
Hazardous Area Classification
WARNING
WARNING
WARNING
(7/03) 1-1