Measurement of trip Time tA:
Nominal fault current I N:
Test current type:
Measurement time:
Measurement range:
Resolution:
Tolerancy:
Measurement of trip Current I
Nominal fault current I N:
Measurement Current:
Resolution:
Tolerancy:
Measurement time:
Current cut off:
Rotary Field
Nominal Voltage:
Max. difference of
voltage U12, U23, U31:
Subject to technical changes without notice!
06/2009
10, 0.5x 30, 30, 5x 30, 100, 300, 500mA Standard
100, 300, 500mA selctive
AC
500ms, not at: 0.5x 30mA - 1999ms, 5x 30mA - 50ms
each 300ms when measuring trip time
1 ... tmax, tmax is th max. test time.
1ms
± (2% v. M. + 2 digit)
:
10, 30, 100, 300, 500mA Standard
40 ... 140% of the nominal fault current I N
10% IΔN
-0% ... +10%
max. each 300ms
immediately for RCD tripping or when exeeding
contact voltage (25V / 50V)
100V ... 440V, 3~, 50 ... 60Hz
± 50%
54