2.2

Rated data

Input data

Basis of the data
Mains
3/PE AC
3/PE AC
Type
ELCAFHI7514
ELCAFHI1524
ELCAFHI3024
Typ
ELCAFHI7514
ELCAFHI1524
ELCAFHI3024
1)
Ta1 = max. 40 °C ambient temperature during operation
2)
Ta2 = max. 55 °C ambient temperature during operation
Typ
ELCAFHI7514
ELCAFHI1524
ELCAFHI3024
1)
No digital inputs and outputs connected
2)
All digital inputs and outputs connected
EDKLCFH3024−EPM DE/EN 2.0
Voltage
U
[V]
LN
400
320 − 0 % ... 440 + 0 %
500
400 − 0 % ... 550 + 0 %
Voltage
Frequency
[V]
[Hz]
400/500
50/60
400/500
50/60
400/500
50/60
Supply voltage for control electronics of the controller
(safely separated power supply unit SELV/PELV)
Voltage range U
[V DC]
DC
+ 24
(+19.2 − 0 % ... +28.8 + 0 %)
l
Technical data
Voltage range
U
[V]
LN
Cyclic mains switching
Max. 5 switchings / 5 minutes
1)
Current (T
)
a1
[A]
3.3/2.6
5.5/4.4
9.0/7.9
Current consumption at + 24 V DC [A]
1)
Min.
1.9
2
Rated data
Frequency range
f [Hz]
45 − 0 % ... 65 + 0 %
45 − 0 % ... 65 + 0 %
2)
Current (T
)
Number
a2
of phases
[A]
2.1/1.6
3
3.4/2.8
3
5.6/4.9
3
2)
Max.
4.4
61