Herunterladen Inhalt Inhalt Diese Seite drucken

3-Phase Mains Connection 230/240 V; Rated Data - Lenze i500 Serie Montage- Und Einschaltanleitung

Vorschau ausblenden Andere Handbücher für i500 Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3-phase mains connection 230/240 V

I5xAExxxD inverters do not have an integrated EMC filter in the AC mains supply.
In order to comply with the EMC requirements according to EN 61800−3, an external EMC filter
according to IEC EN 60939 has to be used.
The user must prove that the EN 61800−3 requirements for conformity are fulfilled.

Rated data

The output currents apply to these operating conditions:
• At a switching frequency of 2 kHz or 4 kHz: Max. ambient temperature 45°C.
• At a switching frequency of 8 kHz or 16 kHz: Max. ambient temperature 40 °C.
Inverter
Rated power
Mains voltage range
Rated mains current
without mains choke
with mains choke
Apparent output power
Output current
2 kHz
4 kHz
8 kHz
16 kHz
Power loss
4 kHz
8 kHz
at controller inhibit
Overcurrent cycle 180 s
Max. output current
Overload time
Recovery time
Max. output current dur-
ing the recovery time
Overcurrent cycle 15 s
Max. output current
Overload time
Recovery time
Max. output current dur-
ing the recovery time
Brake chopper
Max. output current
Min. brake resistance
Max. motor cable length
shielded
without EMC category
Weight
I55AE240C
kW
A
A
kVA
A
A
A
A
W
W
W
A
s
s
A
A
s
s
A
A
Ω
m
kg
4
3/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
20.6
15.7
6.4
16.5
16.5
16.5
11
115
130
6
24.8
60
120
12.4
33
3
12
12.4
26
15
50
2.1
Technical data
3-phase mains connection 230/240 V
I55AE255C
5.5
28.8
21.9
8.7
23
23
23
15.3
175
195
6
34.5
60
120
17.3
46
3
12
17.3
26
15
Rated data