Herunterladen Inhalt Inhalt Diese Seite drucken

Modbus Rtu - Lenze i500 Serie Montage- Und Einschaltanleitung

Vorschau ausblenden Andere Handbücher für i500 Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mounting/ installation
Electrical installation

Modbus RTU

Modbus RTU
Typical topologies
A1
120
X216
TA
TB
COM
Terminal description
Connection
Connection type
Min. cable cross-section
Max. cable cross-section
Stripping length
Tightening torque
Required tool
Basic network settings
Use the DIP switch to set the node address and baud rate and to activate the integrated bus terminating
resistor.
Bus termination
R
c
OFF
n.c.
Inactive
ON
Active
Bold print = default setting
The network must be terminated with a 120 Ω resistor at the physically first and last node.
Set the "R" switch to ON at these nodes.
60
A2
120
X216
TA
TB
COM
mm²
mm²
mm
Nm
c
b
R
Mode
Baud rate
b
OFF
Automatic detection
ON
Value from parameter
Line
A3
120
X216
TA
TB
Modbus
X216
pluggable spring terminal
0.5
2.5
10
0.4 x 2.5
a 128
64 32 16 8
4
2
Address
Parity
a
128
OFF
OFF OFF OFF OFF OFF OFF OFF OFF
Automatic detection
ON
Node address - example:
Value from parameter
OFF
Node address = 16 + 4 + 2 + 1 = 23
Node address > 247: value from parameter
An
X216
COM
-
1
O
N
Modbus node address
64
32
16
8
Value from parameter
OFF
OFF
ON
OFF
120
TA
TB
COM
4
2
1
ON
ON
ON

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis