CAN port
)
Note!
Only connect terminals of the same signal type.
ƒ
For further information with regard to the CAN bus system please refer to
ƒ
the CAN Communication Manual.
We recommend the use of CAN cables according to ISO 11898−2.
1
6
IPC001
MPI port
)
Note!
For more information on the MPI port, please see the Siemens S7 System
ƒ
Manual.
Please follow the specifications of the PROFIBUS user organisation (PNO) for signal cables.
1
6
IPC001
LDCDS−EL100MA DE/EN 2.2
Installation
Electrical installation
Description
CAN bus connection
Pin 1: Not assigned
Pin 2: CAN−LOW (LO)
Pin 3: CAN−GND (CG)
Pin 4 ... 6: Not assigned
Pin 7: CAN−HIGH (HI)
Pin 8 ... 9: Not assigned
Description
MPI connection
Pin 1 ... 2: Not assigned
Pin 3: RxD/TxD−P (B)
Pin 4: RTS
Pin 5: M5V
Pin 6: P5V
Pin 7: Not assigned
Pin 8: RxD/TxD−N (A)
Pin 9: Not assigned
Connection type
9−pole Sub−D plug
Connection type
9−pole Sub−D socket
33
Cable type
CAN cable acc. to
ISO 11898−2 with
9−pole Sub−D socket
Cable type
According to
specification of the
Siemens company
l