Electrical installation
Power connections E82EV153K4B ... E82EV303K4B
5.2
Power connections of E82EV153K4B ... E82EV303K4B
5.2.1
Mains connection
Connection with mains choke
Connection with subassembled mains filter
Connection with built-on assembled mains filter
Fuses and cable cross-sections
Type
mains
1)
E82EV153K4B2x1
3/PE AC 320 V -0 % ... 550 V +0 %
2)
E82EV153K4B2x1
45 Hz -0 % ... 65 Hz +0 %
2)
E82EV223K4B2x1
DC 450 V -0 % ... 775 V +0 %
2)
E82EV303K4B2x1
1)
Without mains choke
2)
With mains choke
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
Please observe the following when using e.l.c.bs.:
•
E.l.c.bs must only be installed between mains supply and controller.
•
Earth leakage circuit breakers can be activated although not required by
– capacitive compensating currents of the cable shields during operation (especially with long,
shielded motor cables),
– simultaneous connection of several controllers to the mains supply,
– use of additional RFI filters.
78
Connection brake chopper ( Operating Instructions for the brake chopper )
Connection mains filter temperature monitoring with PTC thermistor
Z1 Mains choke/mains filter
Installation to EN 60204-1
Fuse
L1, L2, L3, PE [mm
M63 A
25
M35 A
10
M50 A
16
M80 A
25
3)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: 500 ... 600 V, tripping characteristic "H" or "K5"
4)
All-current sensitive e.l.c.b.
EDK82EV903 DE/EN/FR 2.1
3)
Installation to UL
2
]
Fuse
L1, L2, L3, PE [AWG]
63 A
4
35 A
8
50 A
6
80 A
3
8200vec288
4)
FI
≥300 mA
L