5
Electrical installation
Wiring of digital frequency input / digital frequency output
5.11
Wiring of digital frequency input / digital frequency output
Installation material required from the scope of supply:
Description
Protective cover
Technical data
Field
Connection at drive controller
Pin assignment
Output frequency
Signal
Load capacity
Special features
Internal voltage source
(X10/4, X10/5)
Field
Connection at drive controller
Input frequency
Signal
Signal evaluation
Current consumption
Special features
Wiring
)
Note!
ƒ
ƒ
214
Use
Protection for unused Sub−D connections
Digital frequency output X10
Connector: Socket, 9−pole, Sub−D
Dependent on the selected basic configuration
0 ... 500 kHz
Two−track with inverse 5 V signals (RS422) and zero track
Max. 20 mA per channel
(up to 3 slave drives can be connected)
The "Enable" output signal at X10/8 switches to LOW if the drive
controller is not ready for operation (e.g. disconnected from mains). This
can trip SD3 monitoring on the slave drive.
DC 5 V / max. 50 mA
Total current at X9/4, X9/5 and X10/4, X10/5: max. 200 mA
Digital frequency input X9
Connector: Pin, 9−pole, Sub−D
0 ... 500 kHz (TTL level)
Two−track with inverse 5 V signals (RS422) and zero track
Via code C0427
Max. 5 mA
With activated SD3 monitoring, TRIP or warning is tripped if the "Lamp
Control" input signal at X9/8 switches to LOW.
Due to this the drive controller can respond if the master drive is not ready
for operation.
We recommend to use Lenze system cables for wiring.
For self−made cables only use cables with shielded cores twisted in pairs.
l
Quantity
4
EDKVS9332X DE/EN/FR 8.0