5
Electrical installation
Wiring of the control connections
Terminal data
Analog inputs, analog outputs
Terminal
Description
X6/1
Analog input 1
X6/2
X6/3
Analog input 2
X6/4
X6/62
Analog output 1
X6/63
Analog output 2
X6/7
GND1
208
Field
Voltage range
Level
Resolution
Current range
Level
Resolution
Voltage range
Level
Resolution
Level
Load capacity
Resolution
Cycle time
Level
Load capacity
Resolution
Cycle time
Reference potential for analog signals
Isolated to X5/39 (GND2)
l
Values
−10 V ... +10 V
5 mV (11 Bit + sign)
−20 mA ... +20 mA
m
20
A (10 Bit + sign)
−10 V ... +10 V
5 mV (11 Bit + sign)
−10 V ... +10 V
Maximum 2 mA
20 mV (9 bits + sign)
1 ms (smoothing time t = 2 ms)
−10 V ... +10 V
Maximum 2 mA
20 mV (9 bits + sign)
1 ms (smoothing time t = 2 ms)
EDKVS9332X DE/EN/FR 8.0